X530 Digital Inputs; X540 Auxiliary Voltage For The Digital Inputs - Siemens SINAMICS Equipment Manual

Medium-voltage drives, supplementary component descriptions
Hide thumbs Also See for SINAMICS:
Table of Contents

Advertisement

5.2.2.8

X530 digital inputs

Table 5-16
Type: Screw terminal 1
DI: digital input; M: electronics ground; M2: reference potential
1)
Note
Ensuring the function of digital inputs
An open input is interpreted as "low".
To enable the digital inputs (DI) to function, terminal M2 must be connected.
This is achieved by using one of the following measures:
1. Providing the ground reference of the digital inputs
2. A jumper to terminal M
Note: This removes isolation for these digital inputs.
5.2.2.9

X540 auxiliary voltage for the digital inputs

Table 5-17
Type: Screw terminal 1
Supplementary component descriptions
Manual, 06/2019
X530: Digital inputs
Terminal
Designation
1
DI 4
2
DI 5
3
DI 6
4
DI 7
5
M2
6
M
X540: Auxiliary voltage for digital inputs
Terminal
Designation
8
+24 V
7
+24 V
6
+24 V
5
+24 V
4
+24 V
3
+24 V
2
+24 V
1
+24 V
Technical data
1)
Voltage: -3 ... +30 V DC
Electrical isolation: Yes
Reference potential: M2
Input characteristic acc. to IEC 61131-2, type 1
Input voltage (including ripple)
"1" signal: 15 ... 30 V
"0" signal: -3 ... +5 V
Input current
at 24 V DC: typ. 9 mA
at <0.5 mA: Signal "0" reliably detected
Input delay
for "0" → "1": typ. 50 µs/max. 100 µs
for "1" → "0": typ. 130 µs/max. 150 µs
Technical data
Voltage: +24 V DC
Max. total load current of +24 V auxili‐
ary voltage for terminals X540 and
X541 combined: 150 mA
Terminal Modules