Note
The power supply for the analog inputs can be taken internally or from an external power supply
unit
5.2.2.5

S5 current/voltage changeover switch for analog inputs

Table 5-13
5.2.2.6

X522 analog outputs/temperature sensor

Table 5-14
X522: Analog outputs/temperature sensor
Terminal
1
2
3
4
5
6
7
8
Type: Screw terminal 1
AO xV: analog output voltage; AO xC: analog output current
1)
Accuracy of the temperature measurement:
2)
- KTY: ±7 °C (including evaluation)
- Pt1000: ±5 °C (Pt1000 tolerance class B according to EN 60751 including evaluation)
- PTC: ±5 °C (including evaluation)
NOTICE
Damage or malfunctions through impermissible voltage values
If the back EMF is impermissible then damage and malfunctions may occur on the
components.
● The back EMF at the outputs may only be in the range between -15 V and +15 V.
Supplementary component descriptions
Manual, 06/2019
Current/voltage selector S5
Switch
S5.0
S5.1
Designation
Technical data
1)
AO 0V+
You can set the following output signals using parameters:
Voltage: -10 ... +10 V (max. 3 mA)
AO 0-
Current 1: 4 ... 20 mA (max. load resistance ≤ 500 Ω)
AO 0C+
Current 2: -20 ... +20 mA (max. load resistance ≤ 500 Ω)
AO 1V+
Current 3: 0 ... 20 mA (max. load resistance ≤ 500 Ω)
AO 1-
Resolution: 11 bits + sign
AO 1C+
Continuously short-circuit proof
+ Temp
KTY84-130 / Pt1000 / PTC temperature sensors
2)
Measuring current through temperature sensor connection: 2 mA
- Temp
2)
5.2 Terminal Module TM31
Function
Selector voltage (V)/current (I) Al0
Selector voltage (V)/current (I) Al1
Terminal Modules