Siemens SINAMICS Equipment Manual page 45

Medium-voltage drives, supplementary component descriptions
Hide thumbs Also See for SINAMICS:
Table of Contents

Advertisement

LED
Color
COM
PROFIdrive
cyclic opera‐
tion
Green
Red
OPT
(OPTION)
Green
Red
RDY and
Red
COM
RDY and
Orange
OPT
DCP = Discovery and Configuration Protocol
1)
DCP is used by PROFINET to determine PROFINET devices and allow basic settings. Therefore this function is only
available on the CU320-2 DP if the CBE20 Option Board is inserted.
Further information can be found in the SINAMICS S120 Function Manual "Communication".
Any individual behaviors of the LED OPT are described for the respective Option Board.
2)
Supplementary component descriptions
Manual, 06/2019
Status
Description, cause
Off
Cyclic communication has not (yet) taken place.
Comment:
PROFIdrive is ready for communication if the Con‐
trol Unit is ready (see LED RDY).
Continuous
Cyclic communication is taking place.
light
Flashing
Full cyclic communication has not yet taken place.
light
Possible causes:
0.5 Hz
● The controller is not transferring any setpoints.
● During isochronous operation, no global control
(GC) or a faulty global control (GC) is
transferred by the controller.
Flashing
PROFIBUS master is sending wrong parameteri‐
light
zation/configuration data
0.5 Hz
Flashing
Cyclic bus communication has been interrupted or
light
could not be established
2 Hz
Off
Electronics power supply is missing or outside the
permissible tolerance range.
Component is not ready.
Option board not installed or no associated drive
object has been created.
Continuous
Option board is ready.
light
Flashing
Depends on the Option Board used
light
0.5 Hz
Continuous
Depends on the Option Board used
light
Flashing
Depends on the Option Board used
light
0.5 Hz
Flashing
At least one fault is present in this component. Op‐
light
tion board not ready (e.g. after switching on).
2 Hz
Flashing
Bus error - communication has been interrupted
light
2 Hz
Flashing
The firmware of the connected option board is be‐
light
ing updated.
0.5 Hz
3.2 Control Unit CU320-2 DP (PROFIBUS)
Remedy
Adapt configuration between
master/controller and CU
Remove fault
Check power supply and/or
component
.
2)
.
2)
.
2)
Remove the fault and acknowl‐
edge
Remove fault
Control Units
43

Hide quick links:

Advertisement

Table of Contents
loading