Terminal Modules
5.3 Terminal Module TM150
5.3.2.2

X500/X501 DRIVE-CLiQ interfaces

Table 5-23
Connector
type
The blanking covers for the DRIVE-CLiQ interfaces are included in the scope of delivery.
Blanking covers (50 units), article number: 6SL3066-4CA00-0AA0
Note
The maximum DRIVE-CLiQ cable length is 100 m.
5.3.2.3

X524 Electronics power supply

Table 5-24
Type: Screw terminal 2
The maximum cable length that can be connected is 30 m.
Note
The two "+" and "M" terminals are jumpered in the connector. This ensures that the supply
voltage is looped through.
74
X500/X501: DRIVE-CLiQ interfaces
Pin
Signal name
1
TXP
2
TXN
3
RXP
4
Reserved, do not use
5
Reserved, do not use
6
RXN
7
Reserved, do not use
8
Reserved, do not use
A
+ (24 V)
B
M (0 V)
DRIVE-CLiQ socket
X524 electronics power supply
Terminal
Designation
+
Electronics power supply
+
+
Electronics power supply
M
Electronics ground
M
Electronics ground
Technical data
Transmit data +
Transmit data -
Receive data +
-
-
Receive data -
-
-
Power supply, max. 450 mA
Electronics ground
Technical data
Voltage: 24 V DC (20.4 ... 28.8 V)
Current consumption (max.): 0.5 A
(including DRIVE-CLiQ)
Max. current via the jumper in the connec‐
tor: 20 A (15 A according to UL/CSA)
Supplementary component descriptions
Manual, 06/2019

Hide quick links: