X127 Lan (Ethernet) - Siemens SINAMICS Equipment Manual

Medium-voltage drives, supplementary component descriptions
Hide thumbs Also See for SINAMICS:
Table of Contents

Advertisement

3.2.2.8

X127 LAN (Ethernet)

Note
Application
Ethernet interface X127 is intended for commissioning and diagnostics, which means that it
must always be accessible (e.g. for service).
Furthermore, the following restrictions apply to X127:
● Only local access is permissible
● No networking - or only local networking is permissible in a locked control cabinet
If remote access to the control cabinet is required, then additional security measures must be
taken to prevent misuse through sabotage, unqualified data manipulation and intercepting
confidential data (see also the Chapter "Industrial Security (Page 9)").
Table 3-22
Connector type: RJ45 socket
Note
The LAN interface does not support auto-MDI(X). If the LAN interface of the communication
partner also cannot handle auto-MDI(X), then a crossover cable must be used to establish the
connection.
For diagnostic purposes, the X127 LAN interface features a green and a yellow LED. These
LEDs indicate the following status information:
Table 3-23
LED
Link port
Activity port
Supplementary component descriptions
Manual, 06/2019
X127 LAN interface (Ethernet)
Pin
Signal name
1
TXP
2
TXN
3
RXP
4
Reserved, do not use
5
Reserved, do not use
6
RXN
7
Reserved, do not use
8
Reserved, do not use
LED statuses for the X127 LAN interface
Color
Status
-
Off
Green
Continuous light
-
Off
Yellow
Flashing light
3.2 Control Unit CU320-2 DP (PROFIBUS)
Technical data
Ethernet transmit data +
Ethernet transmit data -
Ethernet receive data +
-
-
Ethernet receive data -
-
-
Description
Missing or faulty link
10 or 100 Mbit link available
No activity
Sending or receiving
Control Units
37

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents