Error Messages

5.4
Error Messages
If an error occurs during the execution of a command, 000F
class and additional data are stored to Un\G1000 to Un\G1066.
Address
(Decimal)
1000
1001
1002–1066
5.4.1

Unknown command used

The command written to Un\G1000 is unknown.
NOTE
This error will also occur when a command is not supported in this function mode.
Address
(Decimal)
1000
1001
1002–1066
5.4.2

Command or parameter change while CIF was busy

After the command interface (CIF) has received a new command in Un\G1000, it will start to execute
this command with the parameters given in Un\G1001 to Un\G1066.
After the command has been written to Un\G1000, the result Un\G1000 will display "CIF busy" (FFFF
After the command written to Un\G1000 has been processed, the result Un\G1000 will be set to the
corresponding success/failure code and will not contain the value FFFF
If any buffer memory from Un\G1000 to Un\G1066 is accessed by a write access while the CIF is busy,
the data is not written to the buffer memory area and the "Command or parameter change while CIF
was busy" error is displayed in the result buffer memory. This error status must be acknowledged/
reset by a special command to make the CIF available again (refer to the next section 5.4.3 below).
Address
(Decimal)
1000
1001
1002–1066
5.4.3

Clear/Reset the "CIF was busy" error

To reset the CIF after a "Command or parameter change while CIF was busy" error (refer to section
5.4.3 above), FFFF
the command execution. If the command execution is finished, X(n+1)7 will be turned ON.
The CIF is available again if Un\G1000 contains 0000
MELSEC-L Series – CANopen€ Module ME3CAN1-L
Description
000F
(Error)
H
Error Class
Additional data, error class dependent
Description
000F
(Error)
H
Error Class: 0064
H
Unused
Description
000F
(Error)
H
Error Class: FFFF
H
Unused
must be written to Un\G1000. Then Y(n+1)7 must be turned ON in order to trigger
H
is written to Un\G1000, and the error
H
Tab. 5-11:
Storing of error messages in the buffer memory
addresses Un\G1000 to Un\G1066
Tab. 5-12:
Error message when an unknown command is
used
.
H
Tab. 5-13:
Error message when a command or parameter
change was attempted while CIF was busy
.
H
Command Interface
).
H