Detailed Description of the Module
3.3
I/O Signals for the Programmable Controller CPU
3.3.1
List of I/O signals
Note that the I/O numbers (X/Y) shown in this section and thereafter depend on the mounting posi-
tion resp. on the start I/O number or head address of the ME3CAN1-L. This head address has to be
added to the shown I/O numbers.
For example, if the ME3CAN1-L occupies the range from X/Y040 to X/Y05F the head address is X/Y040.
However the least significant digit is omitted and the head address "n" in this case reads as "4". The "mod-
ule ready" input (Xn0) will be X40 and the "EMCY message available" signal (X(n+1)1) will be X51.
Signal direction CPU Module
Device No. (Input)
X(n+1)0
X(n+1)1
X(n+1)2
X(n+1)3
X(n+1)4
X(n+1)5
X(n+1)6
X(n+1)7
X(n+1)8
X(n+1)9
X(n+1)A
X(n+1)B
X(n+1)C
X(n+1)D
X(n+1)E
X(n+1)F
Tab. 3-5:
NOTE
The "Use prohibited" signals cannot be used by the user since they are for system use only.
If these are turned ON/OFF by the sequence program, the performance of the CANopen module
cannot be guaranteed.
3 – 6
Signal name
Xn0
Module ready
Xn1
Data exchange completed
Xn2
Module restart completed
Module in Layer 2 online mode
Xn3
(Layer 2 modes only)
Message transmit trigger completed
Xn4
(Layer 2 modes only)
Xn5
Xn6
Xn7
Xn8
Xn9
Use prohibited
XnA
XnB
XnC
XnD
XnE
XnF
ME3CAN1-L error
NMT Error Control failure available
(CANopen mode only)
EMCY message available
(CANopen mode only)
Time stamp setting completed
(CANopen mode only)
Time stamp information is available in
buffer memory (CANopen mode
only)
Use prohibited
Command execution completed
Use prohibited
Save configuration / restore factory
default completed
I/O signals of the ME3CAN1-L
I/O Signals for the Programmable Controller CPU
ME3CAN1-L
Signal direction CPU Module
Device No. (Output) Signal name
Yn0
Yn1
Yn2
Yn3
Yn4
Yn5
Yn6
Yn7
Yn8
Yn9
YnA
YnB
YnC
YnD
YnE
YnF
Y(n+1)0
Y(n+1)1
Y(n+1)2
Y(n+1)3
Y(n+1)4
Y(n+1)5
Y(n+1)6
Y(n+1)7
Y(n+1)8
Y(n+1)9
Y(n+1)A
Y(n+1)B
Y(n+1)C
Y(n+1)D
Y(n+1)E
Y(n+1)F
ME3CAN1-L
Use prohibited
Data exchange request
Module restart
Layer 2 online mode request
(Layer 2 modes only)
Message transmit trigger request
(Layer 2 modes only)
Use prohibited
ME3CAN1-L error clear request
NMT Error Control failure clear
request (CANopen mode only)
EMCY message area clear request
(CANopen mode only)
Time stamp set request
(CANopen mode only)
Time stamp read request
(CANopen mode only)
Use prohibited
Command execution request
Use prohibited
Save configuration / restore factory
default configuration request
MITSUBISHI ELECTRIC