Detailed Description of the Module
Tab. 3-25: Direct transmit buffer memory access for unsigned and signed 8 bit objects
● Signed and unsigned 16 bit object
Tab. 3-26: Direct transmit buffer memory access for unsigned and signed 16 bit objects
3 – 30
Index (Hexadecimal)
Unsigned 8 bit object
A046
A047
A048
Index (Hexadecimal)
Unsigned 16 bit object
A100
A101
A102
A103
A104
Buffer Memory Details: CANopen€ Mode
Signed 8 bit object
A006
A007
A008
Signed 16 bit object
A0C0
A0C1
A0C2
A0C3
A0C4
Sub-index
Buffer memory address
(Hex.)
(Decimal)
01
lower 8 bit
13762
02
higher 8 bit
:
:
FD
lower 8 bit
13888
FE
higher 8 bit
01
lower 8 bit
13889
02
higher 8 bit
:
:
FD
lower 8 bit
14015
FE
higher 8 bit
01
lower 8 bit
14016
02
higher 8 bit
:
:
0F
lower 8 bit
14023
10
higher 8 bit
Sub-index
Buffer memory address
(Hex.)
(Decimal)
1
13000
2
13001
:
:
FE
13253
1
13254
:
:
FE
13507
1
13508
:
:
FE
13761
1
13762
:
:
FE
14015
1
14016
:
:
08
14023