Input/ Output Connection - Delta Amplon Series User Manual

Single phase 5/6/8/10 kva
Hide thumbs Also See for Amplon Series:
Table of Contents

Advertisement

7.2 Input/ Output Connection

Please see the figures below for input/ output connection.
1
L
AC INPUT
L
UPS OUTPUT
5/ 6kVA
(Suffix 35 Model)
Cable Selection:
2
For the specifications of input/ output cables, please refer to Table 7-1.
Table 7-1: Specifications of Input/ Output Cables
Spec. \ Capacity
Input/ Output Cables
(Rating Temperature 90°C)
Tightening Torque
(For AC Wiring)
Spec. \ Capacity
Input/ Output Cables
Tightening Torque
(For AC Wiring)
In accordance with National Electrical Codes (NEC), please install the suitable
conduits and cable sleeves.
When connecting the input/ output power cords, please observe the following
3
rules.
Amplon RT Series
1
N
L
AC INPUT
N
1
L
UPS OUTPUT
6kVA
(Suffix B8 Model)
UPS OUTPUT
L
2
L
UPS OUTPUT
L1
2
L
5/ 6kVA (Suffix: B8)
#8AWG
12kgf·cm
5/ 6kVA (Suffix: 35)
2
6mm
12kgf·cm
3 6
AC INPUT
N
L
8/ 10kVA
(Suffix 35 Model)
AC INPUT
L2
L1
8/ 10kVA
(Suffix B8 Model)
8/ 10 kVA (Suffix: B8)
#6AWG
25.5kgf·cm
8/ 10 kVA (Suffix: 35)
10mm
18kgf·cm
N
L2
2

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents