Once the UPS runs normally, switch on the output protective device (see
4
Figure 7-1) installed between the UPS and the loads.
NOTE :
To prevent the UPS from activating the overload protection mechanism
during start-up process, please turn on the high-power loads first and
then low-power loads.

8.2 Turn-off

Make sure all of the loads connected to the UPS are off.
1
(1) Press and hold the ON/ OFF button (
2
you hear one beep, (3) use the Scrolling UP or Down button (
select 'Yes' , and (4) press the Enter button (
Switch off the input protective device (see Figure 7-1) and output protective
3
device (see Figure 7-1).
After the LCD backlight goes dim and the fans stop completely, switch off the
4
battery breaker to ensure that there is no remaining battery power.
Press and hold the button
for 3 seconds and release it
after you hear one beep.