Mins; Switch Off The Input Breaker (Q1), Bypass Breaker (Q2) And Output Breaker (Q4) - Delta Modulon DPH series User Manual

Three phase, 100-300 kva
Hide thumbs Also See for Modulon DPH series:
Table of Contents

Advertisement

4
Please log in as an Administrator. For the Administrator password, please contact
service personnel. After login, ensure that you are in the Administrator login status
(see Figure 6-55).
UPS-1.1
MEASUREMENT
Power Flow
POWER FLOW
Maintenance
Power Flow
Bypass
Bypass
Summary
Mains
System Status
90 %

5 mins

EMS
(Figure 6-55: Bypass Mode Screen_ Administrator Login)
5
Go to SETUP
UPS-1.1
MEASUREMENT
MODE SETTING
On-Line
6

Switch OFF the Input Breaker (Q1), Bypass Breaker (Q2) and Output Breaker (Q4).

After that, the UPS will run in Standby mode.
7
Administrator Login
SETUP
MAINTENANCE
Mode Setting
On-Line.
SETUP
MAINTENANCE
Mode Setting
Select to change system mode
Green
ECO
(Figure 6-56: Select Online Mode)
6-39
LOG IN
EVENT LOG
Administrator
Load
30 %
LOG IN
EVENT LOG
Administrator
Energy
Frequency
Recycle
Conversion
6
UPS Operation
10:15
May 25,2018
Bypass
10:15
May 25,2018
Bypass