Delta Amplon Series User Manual page 55

Single phase 5/6/8/10 kva
Hide thumbs Also See for Amplon Series:
Table of Contents

Advertisement

Battery
z
z
Setup Item
Automatic Battery Test
Deep Discharge Test
Low Battery
Warning Capacity
Warning of
Remaining Time
Runtime Limitation
Charge Mode
Float Charging
Voltage
Internal Charging
Current
External Battery Type *
External Battery
Capacity
Install date
NOTE :
* When the External Battery Type is set as Standard battery pack, you
need to configure the Part Number and the Quantity of the standard
battery pack(s).
Chapter 9
Selectable Value
No test/ Daily/ Weekly/
Biweekly/ Monthly
20-90% (one step: 10%)
0-95%
(one step: 5%)
0-60mins
(one step: 1min)
Disable/ 1/ 2/ 3..../ 240
(one step: 1min)
2-stage/ 3-stage
Auto/ Customize
(2.20 - 2.35 V/ cell,
one step: 0.01V)
For 5K/ 6K: 1/ 2/ 3/ 4/ 5/ 6/ 7/ 8
For 8K/ 10K: 1.5/ 2/ 3/ 4/ 5/ 6
Standard battery pack/
Customer own batt. pack
Standard battery pack:
Part Number Quantity
Customer own batt. pack:
Battery Voltage Capacity
YYYY/ MM/ DD
5 1
LCD Display & Settings
Default Value
No test
90%
10%
2mins
Disable
2-stage
Auto
1A (5K/ 6K)
1.5A (8K/ 10K)

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents