Delta Amplon Series User Manual

Hide thumbs Also See for Amplon Series:

Advertisement

Quick Links

The power behind competitiveness
Delta UPS Amplon Family
N Gen3 Series, Single Phase
1/ 2/ 3 kVA
User Manual
www.deltaww.com

Advertisement

Table of Contents
loading

Summary of Contents for Delta Amplon Series

  • Page 1 The power behind competitiveness Delta UPS Amplon Family N Gen3 Series, Single Phase 1/ 2/ 3 kVA User Manual www.deltaww.com...
  • Page 2 User Manual (“Manual”), including but not limited to the contents, information, and figures are solely owned and reserved by Delta Electronics Inc. (“Delta”). The Manual can only be applied to the operation or the use of this product. Any disposition, duplication, dissemination, reproduction, modification, translation, extraction, or usage of this Manual in whole or in part is prohibited without the prior written permission of Delta.
  • Page 3: Table Of Contents

    Table of Contents Table of Contents Chapter 1 : Important Safety Warnings ------------------------ 1 Transportation ------------------------------------ 1 Preparation ---------------------------------------- 1 Installation ---------------------------------------- 1 Operation ----------------------------------------- 2 Maintenance, Service and Faults ------------------ 2 Packing List --------------------------------------- 3 Chapter 2 : Installation and Setup ---------------------------- 4 Rear Panel View ----------------------------------- 4 Operating Principle -------------------------------- 6 Setup the UPS ------------------------------------ 6...
  • Page 4: Chapter 1 : Important Safety Warnings

    (e.g. laser printers) to the UPS output sockets. It is not recommended to connect the UPS with following type of loads. For the load suitability please contact Delta customer service before purchas- ing. 1. Regenerative loads (e.g. CNC machine and lifts) 2.
  • Page 5: Operation

    Chapter 1 Important Safety Warnings When installing the equipment, please ensure that the sum of the leakage current of the UPS and the connected devices does not exceed 3.5mA. 1.4 Operation Do not disconnect the mains on the UPS system or the building wiring out- let (shockproof socket outlet) during operations since this would cancel the protective earthing of the UPS system and of all connected loads.
  • Page 6: Packing List

    - Wear rubber gloves and boots. - Do not lay tools or metal parts on the top of batteries. - Disconnect charging source prior to connecting or disconnecting the battery input terminals. - Remove every battery grounding during installation and maintenance to reduce the likelihood of electric shock.
  • Page 7: Chapter 2 : Installation And Setup

    Chapter 2 Installation and Setup Chapter 2 : Installation and Setup NOTE : Before installation, please inspect the unit. Be sure that nothing inside the package is damaged. Please keep the original package in a safe place for future use. Rear Panel View Standard Runtime Model UPA102N2NX0B035...
  • Page 8 UPA102N2NX0B0B1 UPA202N2NX0B0B1 INPUT BREAKER INPUT BREAKER OUTPUT 10A MAX. INPUT INPUT 10A MAX. 10A MAX. OUTPUT 10A MAX. UPA302N2NX0B0B1 OUTPUT 20A MAX. UPS OUTPUT INPUT BREAKER INPUT 16A MAX. Item AC input Input circuit breaker USB port RS-232 port Mini slot Amplon N Gen3 Series...
  • Page 9: Operating Principle

    Chapter 2 Installation and Setup Item Output socket External battery connector Output terminal REPO Port 2.2 Operating Principle The operating principle of the UPS is shown as below: 2.3 Setup the UPS Step 1: Connection of battery wires (optional) NOTE : Only applicable to models with P/N ending with 0BA.
  • Page 10 If the extended runtime function is to be adopted, please connect external batteries as shown below. INPUT BREAKER TO EXTERNAL INPUT 10A MAX. OUTPUT 10A MAX. BATTERY Please refer to the figure below to secure the battery cable to the terminal with the suitable screws and nuts.
  • Page 11 Chapter 2 Installation and Setup Table 1: Power Cords for Different UPS Models Type of Power Cord UPA102N2NX0B035 1kVA Plug IEC C14 UPA202N2NX0B035 2kVA Plug IEC C14 UPA302N2NX0B035 3kVA Plug IEC C20 UPA102N2NX0B0BA 1kVA Plug IEC C14 UPA202N2NX0B0BB 2kVA Plug 10A Australia UPA102N2NX0B0B1 1kVA Plug 10A Brazil...
  • Page 12 UPS shutdown/ start-up and monitor UPS status via your PC. The UPS is equipped with Mini slot perfect for Delta Mini SNMP, Relay I/ O, or MODBUS cards (optional). After the Mini SNMP is installed in the UPS, advanced communication and monitoring functions will be available.
  • Page 13: Battery Replacement

    Chapter 2 Installation and Setup NOTE : The REPO port can also be used for ROO application, which allows you remotely turn on/ off the inverter. If you need detailed ROO information or ROO setup service, please contact your local dealer or customer service.
  • Page 14: Chapter 3 : Operation

    Chapter 3 : Operation Button Operation ON / MUTE SELECT OFF / ENTER Button Function Turn on the UPS: Press and hold the ON/ MUTE button for at least 2 seconds to turn on the UPS. Mute the alarm: When the UPS is in battery mode, press and hold this button for at least 5 seconds to disable or enable the alarm system.
  • Page 15: Lcd Panel

    Chapter 3 Operation Button Function OFF/ ENTER Confirm selection key: Press this button to confirm selec- Button tion in setting mode. Switch LCD message: Press this button to change the LCD message for input voltage, input frequency, battery volt- age, output voltage and output frequency. It will return to default display when pausing for 10 seconds.
  • Page 16 Display Function Remaining backup time information Indicates the remaining backup time in a pie chart. Indicates the remaining backup time in numbers. H: hour, M: minute, S: second Fault information Indicates that the warning and fault occurs. Indicates the warning and fault codes, and the codes are listed in details in 3.7 fault reference code .
  • Page 17: Audible Alarm

    Chapter 3 Operation Display Function Indicates the bypass circuit is working. Indicates the ECO mode is enabled. Indicates the inverter circuit is working. Indicates the output is working. Battery information Indicates the battery level by 0-25%, 26-50%, 51-75%, and 76-100%. Indicates the battery is fault.
  • Page 18: Lcd Display Wordings Index

    3.4 LCD Display Wordings Index Abbreviation Display Content Meaning Enable Disable Escape High loss Low loss Battery Converter Temperature Charger Bypass frequency unstable EEPROM error Amplon N Gen3 Series...
  • Page 19: Ups Setting

    Chapter 3 Operation 3.5 UPS Setting There are three parameters to set up the UPS. Parameter 1 Parameter 2 Parameter 3 Parameter 1: It is for function selection. Refer to the table below. Parameter 2 and Parameter 3 are the setting options or values for each program.
  • Page 20 02: Frequency converter enable/ disable Parameter 2 & 3: Enable or disable converter mode. You may choose the following two options. CF ENA: converter mode enable CF DIS: converter mode disable (Default) 03: Output frequency setting Parameter 2 & 3: Output frequency setting. If the battery mode is enabled, you may choose the following initial frequency.
  • Page 21 Chapter 3 Operation 04: ECO enable/ disable Parameter 3: Enable or disable ECO function. You may choose the following two options. ENA: ECO mode enable DIS: ECO mode disable (Default) 05: ECO voltage range setting Parameter 2 & 3: Set an acceptable high voltage point and a low voltage point for ECO mode by pressing the Down key or Up key.
  • Page 22 06: Bypass enable/ disable when the UPS is off Parameter 3: Enable or disable bypass function. You may choose the following two options. ENA: Bypass enable DIS: Bypass disable (Default) 07: Bypass voltage range setting Parameter 2 & 3: Set the acceptable high voltage point and acceptable low voltage point for bypass mode by pressing the Down key or Up key.
  • Page 23 Chapter 3 Operation 08: Discharging time limitation Parameter 3: Set the discharging time limitation in battery mode for general outlets. 0 ~ 999: Set up the discharging time limitation in minutes from 0 ~ 999 for general outlets in battery mode. 0: When setting as “0”, the discharging time will be only 10 seconds.
  • Page 24: Operating Mode Description

    00: Exit Setting Exit the setting mode. 3.6 Operating Mode Description Online Mode When the input voltage is within the acceptable range, the UPS will provide pure sine wave and stable AC power to output. The UPS will also charge the battery in online mode.
  • Page 25: Faults Reference Code

    Chapter 3 Operation Battery Mode When the input voltage is beyond the acceptable range or a power failure has oc- curred, the UPS will backup power from batteries and an alarm will be sounding every 4 seconds. Bypass Mode When the input voltage is within the acceptable range but the UPS is overloaded, the UPS will enter bypass...
  • Page 26: Warning Indicator

    Fault Event Error Code Icon Inverter output short Battery voltage too high Battery voltage too low Over temperature Overload Charger failure 3.8 Warning Indicator Warning Icon (flashing) Alarm Low battery Sounding every second Sounding twice every Overload second Battery is not connected Sounding every second Over charge Sounding every second...
  • Page 27: Chapter 4 : Optional Accessories

    Chapter 4 Optional Accessories Chapter 4 : Optional Accessories Item Function Mini SNMP Monitoring and control for the status of the UPS IPv6 Card via a network system. Mini Relay Increase of the dry contact number. I/O Card Provision of the MODBUS communication Mini MODBUS Card function for the UPS.
  • Page 28: Chapter 5 : Troubleshooting

    Chapter 5 : Troubleshooting When an error occurs, please follow the table below to solve the according issues. Symptom Possible Cause Remedy Check if the input The AC input power is not power cord firmly connected well. connected to the No indication and mains.
  • Page 29 Chapter 5 Troubleshooting Symptom Possible Cause Remedy Error code 43 is shown and the The UPS shuts down Remove excess loads automatically because icon is lighting from the UPS output on the LCD display of overload at the UPS and restart it. and the alarm is con- output.
  • Page 30: Chapter 6 : Storage And Maintenance

    Chapter 6 : Storage and Maintenance Operation The UPS system contains no user-serviceable parts. If the battery service life (3~5 years at 25°C ambient temperature) has been exceeded, the batteries must be replaced. In this case, please contact your dealer. NOTE : Be sure to deliver the spent battery to a recycling facility or ship it to your dealer in the replacement battery packing material.
  • Page 31: Appendix 1 : Technical Specifications

    Appendix 1 : Technical Specifications Appendix 1 : Technical Specifications Model NX 1kVA NX 2kVA NX 3kVA 1000VA/ 2000VA/ 3000VA/ Capacity 900W 1800W 2700W Voltage 120-285 Vac (Based on load at 50%) Range 180-285 Vac (Based on load at 100%) Frequency 40 ~ 70 Hz Range...
  • Page 32 Model NX 1kVA NX 2kVA NX 3kVA Current 3:1 (max) Crest Ratio ≤ 3% (linear load); Harmonic Output Distortion ≤ 6% (non-linear load) Waveform Pure Sinewave (Batt. Mode) AC Mode Efficiency ECO Mode Battery Voltage Recharge Battery* 4 hours recover to 90% capacity (Typical) Time Charging Current...
  • Page 33 Appendix 1 : Technical Specifications Model NX 1kVA NX 2kVA NX 3kVA Storage -20 ~ 50°C (-4 ~ 122°F) Temperature Storage Environment Relative Humidity 10 ~ 90% Humidity Noise Level < 50 dBA (AC mode) NOTE : 1. * The rated output power of the UPS needs to be de-rated to 70%.
  • Page 34: Appendix 2 : Warranty

    Appendix 2 : Warranty Seller warrants this product, if used in accordance with all applicable instructions, to be free from original defects in material and workmanship within the warranty period. If the product has any failure problem within the warranty period, Seller will repair or replace the product at its sole discretion according to the failure situation.