Delta Amplon Series User Manual page 66

Single phase 5/6/8/10 kva
Hide thumbs Also See for Amplon Series:
Table of Contents

Advertisement

Error
Code
0x1101
0xA000 Charger Fault
0x8106
0X6100
0x1003
NOTE :
If all possible causes are eliminated but the alarm still appears, please
contact your local dealer or customer service.
Amplon RT Series
Alarm
Message
Output Overload
Shutdown
INV IGBT Over
Heat Shutdown
PFC Over Heat
Shutdown
Battery
Disconnected
Possible
Cause
The UPS is over-
loaded.
The UPS has an
internal fault.
1. The vents are
blocked.
2. The UPS has an
internal fault.
1. The vents are
blocked.
2. The UPS has an
internal fault.
1. The UPS is
not properly
connected to the
external battery
pack(s).
2. The battery/
batteries is (are)
damaged.
6 2
Solution
Check the power
consumption of the
loads, and remove
the unnecessary
loads.
Please contact
service personnel.
1. Check whether the
vents are blocked.
2 Contact service
personnel.
1. Check whether the
vents are blocked.
2. Contact service
personnel.
1. Check whether the
UPS is properly
connected to the
external battery
pack(s).
2. Contact service
personnel.