You can choose the setup items such as Output, Input, ECO Mode, On/ Off
Settings, Battery, General, Outlet Control, Dry Contact Setting and Component
Life Prediction to set up relevant settings. For more information about the Setting
Menu, please refer to the tables below for each setup item's relevant default value
and selectable value.
Output
z
z
Setup Items
Output Phase
Output Voltage
Output Frequency
Output Sync.
Freq. Range
Output Freq.
Slew Rate
Output Mode
Standby Mode
Overload Alarm
NOTE :
1. * When the Output Frequency is set as Auto, the output frequency
will vary according to the bypass frequency. If the bypass frequency
is ≥ 55Hz, the Free_Run_Frequency/ Cold_Start_Frequency will be
set as 60Hz.
If the bypass frequency is < 55Hz, the Free_Run_Frequency/ Cold_
Start_Frequency will be set as 50Hz.
2. When the Output Frequency is set as Auto and the Bypass Output
under the Standby Mode item is set as Enable, the bypass output
range will be the same as the Output Sync. Freq. Range.
3. ** When the Output Frequency is set as Converter-50Hz/
Converter-60Hz, the UPS will enter into Frequency Conversion
mode and the bypass output will become Disable.
Selectable Value
1-phase
200V, 208V, 220V,
230V, 240V
Auto* / Converter-50Hz** /
Converter-60Hz**
±0.5/ 1/ 3/ 5Hz
0.5/ 1/ 2/ 3/ 4 Hz/ sec.
Industrial/ IT
No output/ Bypass output
30-105% (one step: 5%)
4 9
Chapter 9
LCD Display & Settings
Default
1-phase
208V for suffix B8 model
230V for suffix 35 model
±3Hz
1 Hz/sec.
Bypass output
105%
Auto
IT