The power behind competitiveness
Delta UPS - Amplon Family
RT Series, Single Phase
5/ 6/ 8/ 10 kVA
User Manual
www.deltapowersolutions.com

Advertisement

Table of Contents
loading

Summary of Contents for Delta Amplon RT Series

  • Page 1 The power behind competitiveness Delta UPS - Amplon Family RT Series, Single Phase 5/ 6/ 8/ 10 kVA User Manual www.deltapowersolutions.com...
  • Page 2 Failure to heed these instructions and warnings will void the warranty. Copyright © 2022 by Delta Electronics Inc. All Rights Reserved. All rights of this User Manual (“Manual”), including but not limited to the contents, information, and figures are solely owned and reserved by Delta Electronics Inc.
  • Page 3: Table Of Contents

    Table of Contents Table of Contents Chapter 1 : Important Safety Instructions --------------------------- 1 Safety Instructions ------------------------------------------------------1 Standard Compliance --------------------------------------------------4 Storage --------------------------------------------------------------------4 Chapter 2 : Introduction --------------------------------------------------- 5 General Overview ------------------------------------------------------5 Exterior & Dimensions -------------------------------------------------5 Package List -------------------------------------------------------------6 Chapter 3 : Operation Panel ---------------------------------------------- 8 LED Indicators -----------------------------------------------------------8 Multi-function Buttons --------------------------------------------------9 LCD Display ------------------------------------------------------------ 12...
  • Page 4 9.2.4 Maintenance Menu--------------------------------------------------------58 Chapter 10 : Optional Accessories -----------------------------------63 Chapter 11 : Troubleshooting -------------------------------------------64 Chapter 12 : Maintenance ------------------------------------------------66 12.1 UPS ---------------------------------------------------------------------- 66 12.2 Batteries ----------------------------------------------------------------- 66 12.3 Fans ---------------------------------------------------------------------- 67 -------------------------------68 Appendix 2 : Warranty ----------------------------------------------------71 Amplon RT Series...
  • Page 5: Chapter 1 : Important Safety Instructions

    Chapter 1 Important Safety Instructions Chapter 1 : Important Safety Instructions 1.1 Safety Instructions Installation Warnings Before installation and usage, please read this User Manual thoroughly. This helps you to use the product correctly and safely. Install the UPS in a well-ventilated area, away from excess moisture, heat, dust, and humidity well-controlled indoor area free of conductive contaminants.
  • Page 6 2. The UPS does not run normally after this User Manual is carefully observed. NOTE : If you use the UPS in an area that generates or incurs dust, you should UPS to ensure normal product life and function. Amplon RT Series...
  • Page 7 Chapter 1 Important Safety Instructions Battery Warnings Keep the batteries away from heat sources. Do not open or mutilate the batter- ies. The released electrolyte is harmful to the skin and eyes and may be toxic. A battery can present a risk of electric shock and high short-circuit current. Servicing of batteries and battery packs must be performed or supervised by qualified service personnel knowledgeable in batteries, battery packs and the required precautions.
  • Page 8: Standard Compliance

    100 % NOTE : After storage and before start-up of the UPS, you must allow the UPS to adjust to room temperature (20°C~25°C or 68°F~77°F) for at least one hour to avoid moisture condensing inside the UPS. Amplon RT Series...
  • Page 9: Chapter 2 : Introduction

    Chapter 2 Introduction Chapter 2 : Introduction 2.1 General Overview The RT series UPS is a single-phase input, single-phase output on-line uninterrupt- ible power supply which provides reliable and consistent sine-wave quality power to your electronic equipment. It adopts the latest technology and the highest quality mode reaches up to 95.5%.
  • Page 10: Package List

    Models: UPS502R2RT0B0B8/ UPS602R2RT0B0B8/ UPS802R2RT0B0B8/ UPS103R2RT0B0B8/ UPS502R2RT0B035/ UPS602R2RT0B035/ UPS802R2RT0B035/ UPS103R2RT0B035 BATTER Y PACK × 4 The power behind competitiveness Delta UPS - Amplon Family RT Series, Single Phase 5/ 6/ 8/ 10 kVA User Manual × 8 × 8 BATTERY PACK www.deltapowersolutions.com...
  • Page 11 Chapter 2 Introduction 5kVA 6kVA 8/ 10kVA 5/ 6kVA 8/ 10kVA Item (0B8) (0B8) (0B8) (035) (035) 1 PC 1 PC 1 PC 1 PC 1 PC User Manual 1 PC 1 PC 1 PC 1 PC 1 PC USB Cable 1 PC 1 PC 1 PC...
  • Page 12: Chapter 3 : Operation Panel

    2. OFF: The output is not protected. 1. ON: The UPS detects an internal fault or an environmental fault. 2. OFF: The UPS is in normal state. 3. Flashing: The UPS shows the warning message(s). Please check the corresponding warning message(s) in Amplon RT Series...
  • Page 13: Multi-Function Buttons

    Chapter 3 Operation Panel 3.2 Multi-function Buttons Multi- function Description Button The button has multiple functions. Please refer to the following for detailed information. 1. Turn-on In standby/ bypass mode, press and hold the button for 3 seconds, release it after you hear one beep and the UPS will run in on-line mode.
  • Page 14 3 (see ), which contains Scrolling related Output information. Up Button In setup up mode, the button is used to navigate the set- ting items. Press the button for 0.1 second to go to the previous setting item. Amplon RT Series...
  • Page 15 Chapter 3 Operation Panel Multi- function Description Button The button is also used to navigate or set up the setting parameter. Press the button for 0.1 second to go to the previous display or to increase a number. If the button is pressed for more than 2 seconds, the number will be increased single digit every 0.2 second automatically until the button is released or the number reaches its highest...
  • Page 16: Lcd Display

    NOTE : If the LCD display goes dim, press any button mentioned above for 0.1 second to wake up the LCD display and enable each button function. 3.3 LCD Display ONLINE Input 232.0V 50.0Hz Output 232.0V 50.0Hz Amplon RT Series...
  • Page 17 Chapter 3 Operation Panel Icon/ Display Description Indicates that the load bank status is ON. Indicates that the load bank status is OFF. Indicates the battery capacity level. 100 % Indicates that the battery is abnormal and needs replacement. If the battery is abnormal, the bat- tery capacity icon ( 100 % Indicates the load level (%).
  • Page 18 Output 232.0V 50.0Hz even if the UPS transfers to online mode or battery mode. BATTERY Runtime Indicates BATTERY mode. Input 0.0V 0.0Hz Output 230.0V 50.0Hz BYPASS Indicates BYPASS mode. Input 232.0V 50.0Hz Output 232.0V 50.0Hz Amplon RT Series...
  • Page 19 Chapter 3 Operation Panel Diagram Description STANDBY Indicates AC STANDBY mode. 100 % Input 232.0V 50.0Hz Output 0.0V 0.0Hz Indicates Frequency Conversion mode. NOTE : Freq. Conv. In Frequency Conversion mode, change according to the UPS input voltage and frequency. However, the text Freq.
  • Page 20: Chapter 4 : Rear Panel

    250V AC 30A OUTPUT SOCKET-1 30A MAX. TMOV AC INPUT MANUAL BYPASS SWITCH NORMAL AC INPUT UPS OUTPUT OUTPUT BREAKER-3 OUTPUT BREAKER-2 OUTPUT SOCKET-3 OUTPUT SOCKET-2 250V AC 30A 250V AC 20A 29A MAX. 20A MAX. UPS OUTPUT Amplon RT Series...
  • Page 21 Chapter 4 Rear Panel Models: UPS502R2RT0B035 & UPS602R2RT0B035 DRY CONTACT REPO RS-485 RS-232 TMOV OUTPUT BREAKER-1 OUTPUT SOCKET-1 250V AC 20A 16A MAX. AC INPUT MANUAL BYPASS SWITCH OUTPUT BREAKER-2 NORMAL 250V AC 25A OUTPUT BREAKER-3 AC INPUT 250V AC 20A UPS OUTPUT OUTPUT BREAKER-4...
  • Page 22 3. For more information, please refer to When emergency events occur, it can shut REPO Port down the UPS safely and immediately. Please refer to for details. Connects to a computer so you can monitor RS-485 Port the UPS status. Amplon RT Series...
  • Page 23 Chapter 4 Rear Panel Item Functions Connects to a computer so you can build up Please refer to for more RS-232 Port information. NOTE : The USB port and the RS-232 port must not be used simultaneously. Connects to a computer so you can monitor parameters and update the management software.
  • Page 24 For UPS grounding. AC Input Terminal Block* (L1 & L2 for Connects to the mains. Input Power Cord Connects to a wall socket. NOTE : * Remove the terminal cover plate and you will see the wiring terminal blocks. Amplon RT Series...
  • Page 25: Chapter 5 : Communication Interfaces

    Chapter 5 Communication Interfaces Chapter 5 : Communication Interfaces NOTE : 1. The UPS can still function properly without making the connections below. 2. For the location of the following communication interfaces, please refer to 5.1 RS-232 Port You can use a RS-232 cable (user supplied) to connect the UPS with a computer and install the UPSentry 2012 software* to check and monitor the UPS status.
  • Page 26: Repo Port

    You can download the software from the following link: http://www.deltapowersolutions.com/en/mcis/ups-software.php. 2. Do not use the USB port and the RS-232 port simultaneously. If you connect the USB cable (user-supplied) to the USB port, the RS-232 port will be disabled right away. Amplon RT Series...
  • Page 27: Dry Contacts

    Chapter 5 Communication Interfaces 5.5 Dry Contacts The RT UPS provides one input dry contact for you to receive external control signals. You can set up relevant items in the Dry Contact Setting screen, which includes Disable/ ROO/ RPO/ Remote shutdown/ Forced bypass/ On generator. events.
  • Page 28 When the output of Standby mode is set as “bypass output”, this command will be ignored. NOTE : During time delay, if UPS receive auto start command, command then do the re-start action. Amplon RT Series...
  • Page 29: External Battery Connector

    Chapter 5 Communication Interfaces Function Description UPS will go to bypass mode immediately and stay there regardless of the bypass state without any time delay. Forced Bypass NOTE : For this item, there is no setting for “time delay”. UPS reduces the sensitivity of input voltage detection to stay at On-Line mode without any time delay.
  • Page 30 1. To increase the battery backup time, you can connect several external battery packs to the UPS. 2. Delta external battery pack is optional. Please refer to the Quick Guide, User Manual or Installation & Operation Guide included in the package of the external battery pack.
  • Page 31 Chapter 5 Communication Interfaces NOTE : battery pack replacement. 2. A battery can present a risk of electric shock and high short-circuit current. 3. Servicing of batteries and battery packs must be performed or battery packs and the required precautions. Keep unauthorized personnel away from batteries and battery packs.
  • Page 32 Please follow the route below to execute the manual battery test in order to clear the alarm. Route: press the button Maintenance Test Start Battery Test. Fore relevant information, please refer Amplon RT Series...
  • Page 33: Chapter 6 : Installation

    Chapter 6 Installation Chapter 6 : Installation Please refer to the system block diagram and related information below for correct installation. Bypass Inverter relay A2D&D2D Inverter Input relay Output load 1 Output Input I/ P Output load 2 Output relay Communication Board Internal...
  • Page 34 : Fix the rail on the rack. Step : Insert the UPS in the rack and tighten the screws. If you want to use a non-Delta rail kit, please only follow step NOTE : If you need the optional rail kit, please contact your local dealer.
  • Page 35: Tower Mounting

    × 4 PCS Tower Stand Tower Stand Expander × 4 PCS Expander × 6 PCS Pull out the two panels and the two Delta logo nameplates , rotate them 90° clockwise and re-insert them (see Delta Logo Nameplate × 2...
  • Page 36 Carefully lift the whole unit upright with the Delta logo nameplates and the icons shown on the panels facing up. Panel × 2 Facing Up Lift Up 90 Delta Logo Nameplate × 2 Place the whole unit inside the tower stands Leave adequate space (at least 50 cm) around all sides of the unit for good ventilation.
  • Page 37: Pdb Disassembly & Installation

    6.3 PDB Disassembly & Installation 6.3.1 Precautions Prior to PDB Disassembly 1. The PDB is assembled with the UPS when it is shipped out from the Delta factory. Disassembly of the PDB must be performed by trained professional personnel. 2. To carry out UPS maintenance without interrupting its power supply, please follow the procedures below to turn the PDB’s manual bypass switch to the...
  • Page 38: Pdb Disassembly

    Disassemble the PDB from the rear of battery pack (see Rear of Battery Pack 3 0A R -1 R -1 R -4 R -4 R -3 R -3 E T- U TP R -2 E T- E T- E T- Screw × 4 Amplon RT Series...
  • Page 39: Pdb Assembly

    Chapter 6 Installation 6.3.3 PDB Assembly Align the PDB’s three holes ( ) with the three guideposts ( ) on the rear of battery pack. Attach the PDB to the rear of the battery pack, and use a cross-head screwdriver ( ) and four screws ( battery pack (see R -1...
  • Page 40: Battery/ Battery Pack Replacement

    2. A battery can present a risk of electric shock and high short-circuit current. 3. Servicing of batteries and battery packs must be performed or supervised and the required precautions. Keep unauthorized personnel away from batteries and battery packs. Amplon RT Series...
  • Page 41 Chapter 6 Installation Replace the battery/ battery pack by following the procedures below. Unscrew the screws and remove the battery pack’s front bezel Disconnect the battery terminals Use the Phillips screwdriver to remove the screws from the protective cover located in front of the battery Pull out the battery from the left battery compartment and insert a new one.
  • Page 42: Chapter 7 : Connection And Wiring

    Utility AC Device Power The protective devices must use approved components that meet safety The power supplying to the UPS must be single-phase in accordance with the unit's rating label, and the UPS must be properly grounded. Amplon RT Series...
  • Page 43: Input/ Output Connection

    Chapter 7 Connection and Wiring 7.2 Input/ Output Connection UPS OUTPUT AC INPUT 8/ 10kVA AC INPUT AC INPUT (Suffix 35 Model) UPS OUTPUT AC INPUT UPS OUTPUT UPS OUTPUT 5/ 6kVA 6kVA (Suffix 35 Model) (Suffix B8 Model) 8/ 10kVA (Suffix B8 Model) Cable Selection: Spec.
  • Page 44 Before Working on This Circuit -Isolate Uninterruptible Power System (UPS) -Then check for Hazardous Voltage between all terminals including the protective earth. Risk of Voltage Backfeed Backfeed Protection Device Requirements: Suggested Backfeed Suggested Model Protection Device Rating Voltage/ Current AF52-30-13 (ABB) Amplon RT Series...
  • Page 45 Chapter 7 Connection and Wiring Suggested Backfeed Suggested Model Protection Device Rating Voltage/ Current AF52-30-13 (ABB) Control Relay Requirements: Breaking Capacity Contact Form Normally Closed (NC) Coil Suggested Model No. HF13F-012-1Z1T Backfeed Protection Wiring Diagram: Please refer to the diagram below to install the backfeed protection device between the AC input and the UPS.
  • Page 46: Chapter 8 : Operation

    Press and hold the ON/ OFF button ( ) for 3 seconds to start up the UPS. Release the button after you hear one beep and the UPS will start up. After the UPS performs self-diagnosis, the UPS will run in ON-LINE mode. Amplon RT Series...
  • Page 47 Chapter 8 Operation BYPASS Input 232.0V 50.0Hz Output 232.0V 50.0Hz Press and hold the button for 3 seconds and release it after you hear one beep. Self Diagnosis In Progress... ONLINE 0x1012 Battery Test Fail Once the UPS runs normally, switch on the output protective device (see ) installed between the UPS and the loads.
  • Page 48 (3) use the Scrolling UP or Down button ( ) to select 'Yes' , and (4) press the Enter button ( ) and output protective device (see battery breaker to ensure that there is no remaining battery power. Amplon RT Series...
  • Page 49: Operation Mode

    Chapter 8 Operation 8.3 Operation Mode Standby Mode After the UPS is connected to the utility AC power, it will supply power to the UPS and the batteries will be charged. Online Mode In on-line mode, the connected loads are supplied by the inverter, which derives its power from the utility AC power, and the UPS charges the batteries and provides power protection to its connected loads.
  • Page 50: Chapter 9 : Lcd Display & Settings

    After you configure the Language, Date & Time, Output Setting, External Battery Type and External Battery Capacity settings, the LCD display will move to the Main Screen that shows the current operation mode. Amplon RT Series...
  • Page 51 50.0Hz Next Output 0.0V 0.0Hz The Initial Setting Screen when the UPS is powered on, the LCD display will show DELTA welcome page for 3 seconds and then directly go to the Main Screen that shows the current operation mode.
  • Page 52: Main Menu

    Output 232.0V 50.0Hz 9.2 Main Menu In the Main Screen, press the button for 0.1 second to enter into the Main Menu. You can set up relevant items here. Measurement Setting Main Menu Control Maintenance NOTE : Amplon RT Series...
  • Page 53 Chapter 9 LCD Display & Settings For setup procedures, please refer to the following: In the Main Menu, select the item you want to configure, press the ENTER button for 0.1 second and the UPS will enter into the setup mode. Press the button for 0.1 second or press the button for 0.1 second to...
  • Page 54 Outlets - Group 1 (Level 2) Dry Contact Setting Dry Contact 1 – Input/ Dry Contact 2 – Output/ Dry Contact 3 – Output/ Dry Contact 4 – Output/ Remote Control (Level 2) Component Life Prediction Fan Life Prediction Amplon RT Series...
  • Page 55: Measurement Menu

    Chapter 9 LCD Display & Settings 9.2.1 Measurement Menu In Main Menu, after selecting , press the button to enter into the Measurement Measurement Menu. The Measurement Menu displays the UPS’s status readings, such as Output, Input, Bypass and Battery information. Output Measurement Setting...
  • Page 56 Output Sync. Freq. Range. 3. ** When the Output Frequency is set as Converter-50Hz/ Converter-60Hz, the UPS will enter into Frequency Conversion mode and the bypass output will become Disable. Amplon RT Series...
  • Page 57 Chapter 9 LCD Display & Settings Input Setup Item Selectable Value Default Value Bypass Max. Voltage +10/ 15/ 20% +15% Bypass Min. Voltage -10/ 15/ 20/ 25/ 30/ 35/ 40% -20% ECO Mode Setup Item Selectable Value Default Value ECO Mode Disable/ Enable Disable ECO Max.
  • Page 58 Customer own batt. pack: Install date YYYY/ MM/ DD NOTE : * When the External Battery Type is set as Standard battery pack, you need to configure the Part Number and the Quantity of the standard battery pack(s). Amplon RT Series...
  • Page 59 Chapter 9 LCD Display & Settings - Battery - Battery 3 /4 4 /4 Internal Charging Current Quantity 1.5 A External Battery Type Install Date Standard Battery Pack 2017/11/11 Part Number GES161B151XXX When the External Battery Type is set as Customer own batt. pack, the Part Number and Quantity will be changed accordingly to Battery Voltage and Total Capacity.
  • Page 60 REPO) or delay time 0-999sec (step: 1 sec) Control Option 3: Normally open/ Normally closed (For ROO) NOTE : *For detailed information about option 1, please contact service personnel. Component Life Prediction Setup Item Selectable Value Default Value Fan Life Prediction No/ Yes Amplon RT Series...
  • Page 61: Control Menu

    Chapter 9 LCD Display & Settings 9.2.3 Control Menu In Main Menu, after selecting , press the button to enter into the Control Control Menu. Output Measurement Setting Charger Alarm Control Maintenance The Control Menu refer to the table below for the setup items and selectable values. LEVEL 1 LEVEL 2 LEVEL 3...
  • Page 62: Maintenance Menu

    UPS will reboot immediately Cancel Cancel Reboot 9.2.4 Maintenance Menu In Main Menu, after selecting , press the button to enter into the Maintenance Maintenance Menu. 1 /2 Test Measurement Setting Battery Aging Reset Maintenance Control 2 /2 About Amplon RT Series...
  • Page 63 Chapter 9 LCD Display & Settings The Maintenance Menu provides commands for enabling UPS maintenance functions. It also provides event logs and UPS identification. Please refer to the table below for the setup items and selectable values. LEVEL 1 LEVEL 2 LEVEL 3 LEVEL 4 LEVEL 5...
  • Page 64 Error Description YYYY/MM/DD HH:MM:SS Clear Log Yes/Cancel Model Name: RT-5K UPS - Part No. UPS502R2RT0B035 UPS - Serial No. 1BA0150001 Maintenance UPS - Manufacture Date About YYYY-MM PS Firmware – 06AR004 Battery Summary: Installed YYYY/MM/ Replace YYYY/MM/ Amplon RT Series...
  • Page 65 Chapter 9 LCD Display & Settings For example, if you need to execute a battery test, please go to Test Start Battery Test Test In Progress… Test Result: Pass (or Fail). 1 /2 - Test Test Start Battery Test Battery Aging Deep Discharge Test Reset Local Dry Contact test...
  • Page 66 Test In Progress... Battery Battery 272.0V 72.0V Battery Battery 272.0V 72.0V Press ESC key to Escape Press ESC key to Escape ONLINE ONLINE Alarm 0X1012 01 Input 232.0V 50.0Hz Icon Battery disconnect or need replaced. Output 232.0V 50.0Hz Amplon RT Series...
  • Page 67: Chapter 10 : Optional Accessories

    (includes 2 annular to extend its range. terminals and 2 butt joint connectors) Provides external batteries to let the UPS continue Delta External Battery supplying power to its connected loads when a Pack power outage occurs. Rail Kit NOTE : 1.
  • Page 68: Chapter 11 : Troubleshooting

    1. When a problem occurs, please check if following situations exist before contacting Delta service personnel: Is the main input voltage present? 2. Please have the following information ready if you would like to contact the Delta service personnel: Unit information including model, serial number, etc.
  • Page 69 Chapter 11 Troubleshooting Error Alarm Possible Solution Code Message Cause Check the power consumption of the Output Overload The UPS is over- 0x1101 loads, and remove Shutdown loaded. the unnecessary loads. The UPS has an Please contact 0xA000 Charger Fault internal fault.
  • Page 70: Chapter 12 : Maintenance

    100% ( 100 % NOTE : If the UPS’s internal batteries need to be replaced, please contact qualified service personnel. During battery replacement, the loads connected to the UPS will not be protected if input power fails. Amplon RT Series...
  • Page 71: Fans

    Chapter 12 Maintenance 12.3 Fans Higher temperatures shorten fan life. When the UPS is running, please periodically check if each fan works normally and make sure if the ventilation air can move freely around and through the UPS. If not, contact service personnel to replace the fans. NOTE : Please ask your local dealer or customer service for more maintenance information.
  • Page 72 Terminal Power Factor Unity* 200* /208* Regulation Frequency Output vTHD <2% (linear load) <3% (linear load) Overload < 105%: continuous; 105% ~ 125%: 2 minutes; Capacity 125% ~ 150%: 30 seconds; >150%, 500 ms Cress Factor Amplon RT Series...
  • Page 73 Appendix 1 Model RT-5K RT-6K RT-8K RT-10K 5K: NEMA L6-20 x 2, L6-30 x 1 Con- Output nection Online Mode Up to 95.5% ECO Mode Up to 99% Battery Type lead-acid battery lead-acid battery 5.5/8.5 minutes Backup Time (O/P PF 0.9) 3/5.5 3.5/6 Battery &...
  • Page 74 Temperature Environ- ment Storage -15°C ~ 50°C (5 ~122°F) Temperature Relative 5% ~ 95% (non-condensing) Humidity NOTE : 1. * de-rated to 90% of its capacity. 2. Please refer to the rating label for the safety rating. Amplon RT Series...
  • Page 75: Appendix 2 : Warranty

    Appendix 2 Warranty Appendix 2 : Warranty Seller warrants this product, if used in accordance with all applicable instructions, to be free from original defects in material and workmanship within the warranty period. If the product has any failure problem within the warranty period, Seller will repair or replace the product at its sole discretion according to the failure situation.
  • Page 77 - Regional Office The United States Australia Delta Electronics (Americas) Ltd. Delta Energy Systems Australia Pty Ltd. 46101 Fremont Blvd. Fremont, CA 94538 Unit 20-21, 45 Normanby Road, Notting Hill VIC 3168, Australia T +1 510 344 2157 T +61 3 9543 3720 E ups.na@deltaww.com...