Setup Logs - Danfoss AK-LM 330 Design Manual

Monitoring unit
Hide thumbs Also See for AK-LM 330:
Table of Contents

Advertisement

Setup logs

Go to the overview
1.
Press the blue overview button with the log symbol.
Log display
2.
3. New logs
Press the +-button to go on to the next page
Selection of parameters
4.
Press the +-button to go on to the next page
AK-LM 330
RS8FR302 © Danfoss 2015-08
If data need to be collected from some of the set parameters,
this should be done using a logo setting in a system manager.
This can store a larger amount of data.
If you want to set up a log in the monitoring unit, consider the
following:
The log function requires that the clock function is set.
Even a minor power failure will stop the clock.
If you want to ensure that the clock is always set, the controller
must either be installed in a network together with a system
unit or a battery module must be installed.
The top line gives access to definition of new logs and to
changes of already established logs.
The next line enables you to see a selection of the defined logs
Here is the start display for new logs
Start by defining which type of log has to be defined
Here it is determined which parameters have to be included
in the setup of data. Select a function here, then a parameter,
and finish with OK.
65