Supply voltage
Supply voltage is only connected to the controller module. The
supply to the other modules is transmitted via the plug between
the modules. The supply must be 24 V +/-20%. One transformer
must be used for each controller. The transformer must be a class
II. The 24 V must not be shared by other controllers or units. The
analog inputs and outputs are not galvanically separated from the
supply.
The + and – 24V input must not be earthed.
Example continued:
Controller module
+ 2 extension module in 100-series
Transformer size (least)
AK-LM 330
8 VA
4 VA
------
12 VA
RS8FR302 © Danfoss 2015-08
Transformer size
The power consumption grows with the number of modules used:
Module
Type
Controller
Extension module
200-series
Extension module
100-series
Total
Number á
Effect
1
x
8 =
8 VA
_
x
5 =
__ VA
_
x
2 =
__ VA
___ VA