Common data for modules

Supply voltage
Power consumption
Analog inputs
On/off supply voltage inputs
Relay outputs
SPDT
Solid state outputs
Ambient temperature
Enclosure
Weight with screw terminals
Approvals
The mentioned data applies to all modules.
If data is specific, this is mentioned together with the module in question.
Capacitive load
The relays cannot be used for the direct connection of capacitive loads such
as LEDs and on/off control of EC motors.
All loads with a switch mode power supply must be connected with a suit-
able contactor or similar.
10
24 V d.c./a.c. +/- 20%
AK-__ (controller)
AK-XM 101, 102, 107
AK-XM 204, 205
Pt 1000 ohm /0°C
Pressure transmitter type AKS 32R / AKS
2050/ AKS 32 (1-5 V)
Other pressure transmitter:
Ratiometric signal
Min. and max. pressure must be set
Min and max. voltage must be set
Voltage signal 0-10 V
Contact function (On/Off )
Low voltage
0 / 80 V a.c./d.c.
High voltage
0 / 260 V a.c.
AC-1 (ohmic)
AC-15 (inductive)
U
Can be used for loads that are cut in and
out frequently, e.g. :
rail heat, fans and AKV valve
During transport
During operation
Material
Class
Mounting
Modules in100- / 200- / controller-series
EU low voltage directive and EMC require-
ments are complied with
UL 873,
RS8FR302 © Danfoss 2015-08
8 VA
2 VA
5 VA
Resolution: 0.1°C
Accuracy: +/- 0.5°C (between -50°C and +50°C)
Resolution:1 mV
Accuracy +/- 10 mV
Max. connection of 5 pressure transmitters on one module
On at R < 20 ohm
Off at R > 2K ohm
(Gold -plated contacts not necessary)
Off: U < 2 V
On: U > 10 V
Off: U < 24 V
On: U > 80 V
4 A
3 A
Min. 24 V
Max. 230 V
Low and high voltage must not be connected to the same
output group
Max. 240 V a.c. , Min. 48 V a.c.
Max. 0.5 A,
Leak < 1 mA
Max. 1 AKV
-40 to 70°C
-20 to 55°C ,
0 to 95% RH (non condensing)
No shock influences / vibrations
PC / ABS
IP10 , VBG 4
For mounting on panel wall or DIN rail
Ca. 200 g / 500 g / 600 g
LVD tested according to EN 60730
EMC tested
Immunity according to EN 61000-6-2
Emission according to EN 61000-6-3
UL file number: E166834 for XM modules
UL file number: E31024 for LM modules