Check Of Settings - Danfoss AK-LM 330 Design Manual

Monitoring unit
Hide thumbs Also See for AK-LM 330:
Table of Contents

Advertisement

Check of settings

1.Go to the overview
2. Select thermostats
3. Overview for thermostats
4. Move on with settings for thermostat 1
AK-LM 330
!
RS8FR302 © Danfoss 2015-08
Before the control starts, we check that all the settings are as they should
be.
The overview display will now show one line for each of the general
functions. Behind each icon there is a number of displays with the
different settings. It is all these settings that have to be checked.
!
When this function is set to 'YES' , a relay will be reserved which couples
with the thermostat. Definition of the connection point must be done
during the I/O configuration.
(In our example, the setting is NO in Thermostats 1 and 2. And YES in
Thermostat 3).
The two DI inputs are used if the thermostat's alarm function is to be
changed temporarily during daily operation:
• Defrosting signal. Signal on the DI input entails change to Delay Time 2.
• Alarm stop. Signal on the DI input stops alarms.
(In our example, both settings have been used in Thermostat 2. Here the
settings are DI1 and DI2 respectively).
Remember the settings at the bottom of the pages – the ones that can
only be seen via the "Scroll bar". "