Wiring - Danfoss AK-LM 330 Design Manual

Monitoring unit
Hide thumbs Also See for AK-LM 330:
Table of Contents

Advertisement

Mounting and wiring - continued

Wiring

Decide during planning which function is to be connected and
where this will be.
1. Connect inputs and outputs
Here are the tables for the example:
Signal
Module
Air temperature - Saux1
Air temperature - Saux2
Air temperature - Saux3
Voltage signal - U1
Voltage signal - U2
Pressure measurement -
Paux1, to 12 bar
1
Pressure measurement -
Paux2, to 34 bar
Relay for thermostat Saux3
Relay for voltage signal U2
Relay for pressostat Paux2
Alarm relay
Signal
Module
Defrost, DI1 for Saux2
Appliance stopped, DI2 for
Saux2
Alarm signal DI3
2
Alarm signal DI4
Pulse signal - E
3
AK-LM 330
Point
Signal type /
Terminal
Active at
1 (AI 1)
1 - 2
Pt 1000
2 (AI 2)
3 - 4
Pt 1000
3 (AI 3)
5 - 6
4 (AI 4)
7 - 8
Pt 1000
5 (AI 5)
9 - 10
6 (AI 6)
11 - 12
0-10 V
7 (AI 7)
13 - 14
0-10 V
8 (AI 8)
19 - 20
9 (AI 9)
21 - 22
10 (AI 10)
23 - 24
AKS 32R-12
11 (AI 11)
25 - 26
AKS 32R-34
12 (DO 1)
31 - 32
13 (DO 2)
33 - 34
14 (DO 3)
35 - 36
15 (DO 4)
37 - 38
16 (DO 5) 39-40-41
ON
17 (DO6)
42-43-44
ON
18 (DO7)
45-46-47
ON
19 (DO8)
48-49-50
OFF
24
-
25
-
Point
Signal type /
Terminal
Active at
1 (DI 1)
1 - 2
Closed
2 (DI 2)
3 - 4
Closed
3 (DI 3)
5 - 6
Closed
4 (DI 4)
7 - 8
Closed
5 (DI 5)
9 - 10
6 (DI 6)
11 - 12
7 (DI 7)
13 - 14
8 (DI 8)
15 - 16
1 (CI 1)
1 - 2
- - -
2 (CI 2)
3 - 4
3 (CI 3)
5 - 6
4 (CI 4)
7 - 8
5 (CI 5)
9 - 10
6 (CI 6)
11 - 12
7 (cI 7)
13 - 14
8 (cI 8)
15 - 16
RS8FR302 © Danfoss 2015-08
The function of the switch functions can be seen in the last column.