Danfoss AK-LM 330 Design Manual page 52

Monitoring unit
Hide thumbs Also See for AK-LM 330:
Table of Contents

Advertisement

Configuration - continued
5. Configuration of Analog
inputs signals
52
Analog signales
Air temperature - Saux1
Air temperature - Saux2
Air temperature - Saux3
Voltage signal - U1
Voltage signal - U2
Pressure measurement, to 12
bar - Paux1
Pressure measurement, to 34
bar - Paux2
We set up the analog inputs for the sensors.
RS8FR302 © Danfoss 2015-08
Indgang
Modul
Punkt
Type
AI1
1
1
Pt 1000
AI2
1
2
Pt 1000
AI3
1
3
AI4
1
4
Pt 1000
AI5
1
5
AI6
1
6
0-10 V
AI7
1
7
0-10 V
AI8
1
8
AI9
1
9
AI10
1
10
AKS 32R-12
AI11
1
11
AKS 32R-34
5 - Analog inputs
The possible signals are the
following:
Temperature sensors:
Saux 1 - 10
Setting:
• Pt1000
• PTC 1000
Pressure transmitters::
Paux 1 - 5
Setting:
• AKS 32, -1 – 6 Bar
• AKS 32R, -1 – 6 Bar
• AKS 32, - 1 – 9 Bar
• AKS 32R, -1 – 9 Bar
• AKS 32, - 1 – 12 Bar
• AKS 32R, -1 – 12 Bar
• AKS 32, - 1 – 20 Bar
• AKS 32R, -1 – 20 Bar
• AKS 32, - 1 – 34 Bar
• AKS 32R, -1 – 34 Bar
• AKS 32, - 1 – 50 Bar
• AKS 32R, -1 – 50 Bar
• AKS 2050, -1 – 59 Bar
• AKS 2050, -1 – 99 Bar
• AKS 2050, -1 – 159 Bar
• User defined (only ratio-
metric. The min. and max.
values of the pressure
interval must be set).
Voltage signals:
Voltage input 1 - 5
Setting:
• 0 - 5
• 1 - 5
• 0 - 10
• 2 - 10
AK-LM 330