Determine The Connection Points - Danfoss AK-LM 330 Design Manual

Monitoring unit
Hide thumbs Also See for AK-LM 330:
Table of Contents

Advertisement

10

Determine the connection points

All connections must be programmed with module and point, so
in principle it does not matter where the connections are made, as
long as it takes place on a correct type of input or output.
• The controller is the first module, the next one is 2, etc.
• A point is the two or three terminals belonging to an input or
output (e.g. two terminals for a sensor and three terminals for a
relay).
The preparation of the connection diagram and the subsequent
programming (configuration) should take place at the present
time. It is most easily accomplished by filling in the connection
survey for the relevant modules.
Principle:
Name
On module
fx Compressor 1
fx Compressor 2
fx Alarm relay
fx Main switch
fx P0
The connection survey from the controller and any extension
modules are uploaded from the paragraph "Module survey. E.g.
controller module:
Signal
- Columns 1, 2, 3 and 5 are used for the programming.
- Columns 2 and 4 are used for the connection diagram.
Signal
Air temperature - Saux1
Air temperature - Saux2
Air temperature - Saux3
Voltage signal - U1
Voltage signal - U2
Pressure measurement -
Paux1, to 12 bar
Pressure measurement -
Paux2, to 34 bar
Relay for thermostat Saux3
Relay for voltage for signal U2
Relay for pressostat Paux2
Alarm relay
AK-LM 330
On Point
Function
x
x
ON
x
x
ON
x
x
OFF
x
x
Close
x
x
AKS 32R 1-6 bar
Module
Point
Terminal
1 (AI 1)
1 - 2
2 (AI 2)
3 - 4
3 (AI 3)
5 - 6
4 (AI 4)
7 - 8
Module
Point
Terminal
1 (AI 1)
1 - 2
2 (AI 2)
3 - 4
3 (AI 3)
5 - 6
4 (AI 4)
7 - 8
5 (AI 5)
9 - 10
6 (AI 6)
11 - 12
7 (AI 7)
13 - 14
8 (AI 8)
19 - 20
9 (AI 9)
21 - 22
10 (AI 10)
23 - 24
1
11 (AI 11)
25 - 26
12 (DO 1)
31 - 32
13 (DO 2)
33 - 34
14 (DO 3)
35 - 36
15 (DO 4)
37 - 38
16 (DO 5) 39 - 40 - 41
17 (DO6)
42 - 43 - 44
18 (DO7)
45 - 46 - 47
19 (DO8)
48 - 49 - 50
24
-
25
-
RS8FR302 © Danfoss 2015-08
Tip
Signal type /
Active at
The Appendix shows 16 general installation types.
If your plant closely resembles one of those shown, you
can use the connection points indicated for it.
Signal
type /
Signal
Active at
Defrost DI1 for Saux2
Pt 1000
Appliance stopped DI2 for
Pt 1000
Saux2
Alarm signal DI3
Pt 1000
Alarm signal DI4
0-10 V
0-10 V
Pulse signal - E
AKS 32R-12
AKS 32R-34
ON
ON
ON
OFF
Module
Point
Mind the numbering.
The right-hand part of the
controller module may look like
a separate module. But it isn't.
Module
Point
Terminal
1 (DI 1)
1 - 2
2 (DI 2)
3 - 4
3 (DI 3)
5 - 6
2
4 (DI 4)
7 - 8
5 (DI 5)
9 - 10
6 (DI 6)
11 - 12
7 (DI 7)
13 - 14
8 (DI 8)
15 - 16
1 (CI 1)
1 - 2
2 (CI 2)
3 - 4
3 (CI 3)
5 - 6
4 (CI 4)
7 - 8
3
5 (CI 5)
9 - 10
6 (CI 6)
11 - 12
7 (cI 7)
13 - 14
8 (cI 8)
15 - 16
Signal type /
Active at
Closed
Closed
Closed
Closed
- - -
35