Danfoss AK-LM 330 Design Manual page 73

Monitoring unit
Hide thumbs Also See for AK-LM 330:
Table of Contents

Advertisement

Read codes
Normally the selected temperature signal can be read from the
display, but under certain conditions the display may show other
codes in order to notify the user of various operating states.
Function
Display readout
OFF
When the "main switch" is set to OFF, the display will read "OFF"
PAS
Requirement for access code. If operation of the display is to be
protected by an access code, both the definition and the access
code must be set in the controllers' authorisation menu for the
local display (LOCD).
Alarm
The three LED's will flash if an alarm is triggered. The alarm code
can be viewed by pressing the top button. Pressing the button will
also reset the alarm relay
- - -
When three dashes appear, the valid temperature reading is faulty
(sensor switched off or short-circuited), or else the display has been
deactivated.
Menu overview:
Parameter
Function
name
r12
Main switch:
0: Controller stopped
1: Regulation
o93
Configuration lock
You can only select a preset configuration or change refriger-
ant when the configuration lock is open.
0 = Configuration open
1 = Configuration locked
o62
Selection of predefined configuration.
This setting will give a choice from a series of predefined
combinations, which at the same time establish the connec-
tion points.
At the end of the manual there is an overview of the options
and connection points.
After configuration of this function, the controller will shut
down and restart.
u1-u31
Readouts for use in service situations
u1
Temperature measurement, thermostat 1
u2
Temperature measurement, thermostat 2
u3
Temperature measurement, thermostat 3
u4
Temperature measurement, thermostat 4
u5
Temperature measurement, thermostat 5
u6
Temperature measurement, thermostat 6
u7
Temperature measurement, thermostat 7
u8
Temperature measurement, thermostat 8
u9
Temperature measurement, thermostat 9
u10
Temperature measurement, thermostat 10
u11
Pressure measurement, pressostat 1
u12
Pressure measurement, pressostat 2
u13
Pressure measurement, pressostat 3
u14
Pressure measurement, pressostat 4
u15
Pressure measurement, pressostat 5
u16
Status on alarm DI 1
u17
Status on alarm DI 2
u18
Status on alarm DI 3
u19
Status on alarm DI 4
u20
Status on alarm DI 5
u21
Status on alarm DI 6
u22
Status on alarm DI 7
u23
Status on alarm DI 8
u24
Status on alarm DI 9
u25
Status on alarm DI 10
u26
Status on alarm DI 11
u27
Status on alarm DI 12
u28
Status on alarm DI 13
u29
Status on alarm DI 14
u30
Status on alarm DI 15
u31
Status on alarm DI 16
.
X = When the controller is not set up, the display will only
read the marked settings
AK-LM 330
At start-
up
x
x
x
RS8FR302 © Danfoss 2015-08
Alarm overview:
A01
High alarm thermostat 1
A02
Low alarm thermostat 1
A03
High alarm thermostat 2
A04
Low alarm thermostat 2
A05
High alarm thermostat 3
A06
Low alarm thermostat 3
A07
High alarm thermostat 4
A08
Low alarm thermostat 4
A09
High alarm thermostat 5
A10
Low alarm thermostat 5
A11
High alarm thermostat 6
A12
Low alarm thermostat 6
A13
High alarm thermostat 7
A14
Low alarm thermostat 7
A15
High alarm thermostat 8
A16
Low alarm thermostat 8
A17
High alarm thermostat 9
A18
Low alarm thermostat 9
A19
High alarm thermostat 10
A20
Low alarm thermostat 10
A21
Low alarm pressostat 1
A22
High alarm pressostat 1
A23
Low alarm pressostat 2
A24
High alarm pressostat 2
A25
Low alarm pressostat 3
A26
High alarm pressostat 3
A27
Low alarm pressostat 4
A28
High alarm pressostat 4
A29
Low alarm pressostat 5
A30
High alarm pressostat 5
A31
Low alarm voltage input 1
A32
High alarm voltage input 1
A33
Low alarm voltage input 2
A34
High alarm voltage input 2
A35
Low alarm voltage input 3
A36
High alarm voltage input 3
A37
Low alarm voltage input 4
A38
High alarm voltage input 4
A39
Low alarm voltage input 5
A40
High alarm voltage input 5
A41
Alarm DI 1
A42
Alarm DI 2
A43
Alarm DI 3
A44
Alarm DI 4
A45
Alarm DI 5
A46
Alarm DI 6
A47
Alarm DI 7
A48
Alarm DI 8
A49
Alarm DI 9
A50
Alarm DI 10
A51
Alarm DI 11
A52
Alarm DI 12
A53
Alarm DI 13
A54
Alarm DI 14
A55
Alarm DI 15
A56
Alarm DI 16
A60
Manual control of DO / DI
E01
Sensor alarm
E02
System alarm
- - 1
Initiation. Display is connected to output A. (- - 2 = output B, etc.)
73