Functions for daily use – Setups/adjustments
This is where you set the functions used for daily operation.
• Time schedule for specifying the store's opening time
This schedule is for sending a signal to selected controllers in
order to tell them that the temperature needs to be adjusted
because covers have been placed over the refrigeration applica-
tions.
The schedule is also used to route alarms. However, this is only
if different alarm destinations have been defined for the day
period and the night period.
• Time schedule for specifying defrost points
The schedule is used to send signals to selected controllers tell-
ing them to start a defrost cycle.
Day / night setup
Control:
If "Started" the signal status will be sent to the EKCs.
Mode:
• If "Auto" is selected, day and night will change automatically.
The signal follows the on/off value on the reference point. See
next setting.
• If "Day" is selected, the controller will always be in daytime
operation.
• If "Night" is selected, the controller will always be in night-time
operation.
Reference point (see "Mode" = auto)
The point which the override signal is to follow is selected here.
If the point is On, the signal status "Day" will be sent to the EKCs.
AK-SM 350 Version 1.7x
Manual RS8EF402 © Danfoss 02-2009
To the end user
These functions are an option, but they are only ap-
plicable if controllers have been installed that can
receive the signals in question.
To the installer
Please put a cross in the box if the functions have
been installed in such a way that they can be oper-
ated from the monitoring unit.
Yes
No
Time schedule
(The schedule is found "one arrow to the right" of "Day/night
setup")
This is where you set the store's opening and closing times. The
times can be used for alarm routing and day/night signals to the
controllers.
The hour setting and minute setting is entered using the arrow
keys.
Day/night signal controllers
(The schedule is found "one arrow to the right" of "Store sched-
ule")
This is where you set the addresses for all the controllers that are
to receive day/night signals
Set address.
(00:000 means no address).