Section 8
Commissioning
8.4.2.3
8.4.2.4
74
Parameter or counter
Parity errors
Overrun errors
Framing errors
Reset counter

Defining Ethernet port settings

Change the Ethernet port settings primarily via PCM600 to ensure
that PCM600 is able to export a consistent configuration to
SYS600. Ethernet port settings are recommended to be changed
only when the device is stand-alone and properly configured.
1.
Select Main menu/Configuration/Communication/Ethernet/Rear port.
2.
Define the settings for the Ethernet port.
IP address
Subnet mask
Default gateway of the optional rear port Ethernet connector

Defining serial port settings

1.
Select Main menu/Configuration/Communication/COM1.
2.
Define the settings for the serial port.
It is possible to change the general serial communication parameters per port.
Select fiber or galvanic mode with the proper baud rate, parity and delays
depending on the system architecture and the selected physical
communication port.
COM1
Serial mode
=RS485 2Wire
Baudrate
=9600
GUID-EA1FA1A1-5067-4719-A351-DBF3D5847E1D V1 EN-US
Figure 50:
Defining the serial port settings
Description
Counts the number of parity errors detected in
characters received
Counts the number of overrun errors detected in
characters received
Counts the number of framing errors detected in
characters received
Resets all counters to zero
A
2NGA000823 A
REX610
Operation Manual