Section 7
Troubleshooting
7.2.2
62

Warnings

In case of a warning, the protection relay continues to operate except for those
protection functions possibly affected by the fault, and the green Ready LED
remains lit as during normal operation.
Warnings are indicated with the text Warning additionally provided with the
name of the warning, a numeric code and the date and time on the LHMI. The
warning indication message can be manually cleared.
If a warning appears, record the name and code so that it can be
provided to ABB customer service.
The display code format for the warning codes is aa.bb.cc.ddd.ee.
aa: Reserved for future
bb: Error domain
1: HW error
2: Runtime error
3: Communication error
cc: Component
Range 0...11
ddd: Warning category
ee: Offset
Range 0...255
Warning
Watchdog reset
Code 00.02.03.010.61
20.1.2021
22:20:34.690
GUID-316DF700-DA41-4807-8882-B5CA65448685 V1 EN-US
Figure 49:
Warning
Table 19:
Warning indications and codes
Warning indication
System
Watchdog reset
Power down det.
Modbus warning
Dataset error
Table continues on next page
Warning category
Additional information
2
Error in file operations
10
Watch dog reset has occurred
11
Auxiliary supply voltage dropped too
low
21
Error in Modbus communication
24
Error in data set(s)
2NGA000823 A
REX610
Operation Manual

Advertisement

Table of Contents
loading

Table of Contents