CHAPTER 5– CONNECTING FIELD DEVICES TO THE I/O BOARD
MultiLoad II Additive Wiring: Inputs
I/O DIGITAL/
I/O 2 METER
ANALOG
METER 0
IO_DA TB2B
IO_2M TB7
✓
✓
+
1
+
1
PORT 4
PORT 4
PORT 4
✓
✓
-
2
-
2
✓
✓
+
3
+
3
PORT 5
PORT 5
PORT 5
✓
✓
-
4
-
4
✓
✓
+
5
+
5
PORT 7
PORT 7
PORT 6
✓
✓
-
6
-
6
✓
+
7
PORT 7
✓
-
8
+
9
PORT 9
-
10
IO_DA TB2A
IO_2M TB6
✓
✓
+
1
+
1
+
2
+
2
12Vdc
✓
-
3
+
3
-
4
+
4
+
5
12Vdc
✓
-
6
-
7
-
8
-
9
-
10
*Note: Most additive injection meters only provide an Open-Collector (pull down) type output. Typically a 1,000 Ohm, ¼ watt pull-up resistor needs
to be added in the pulser junction box to pull this output to 12V+ when the output is off.
Note (I/O 2 METER Only): TB7 pins 3 and 4 can be configured as Port 5 or Port 6. It is only 1 port, but because of the logic in the firmware, it may
be necessary to address it as Port 5 or Port 6 in the configuration.
42
MultiLoad II/ RCU II Explosion Proof Lite (EXL) Installation Guide - Part # 6070
METER 1
IO_2M TB8
PORT 4
✓
+
1
PORT 4.+
1
✓
+
-
2
PORT 4.-
✓
+
3
-
✓
-
4
PORT 5
✓
+
5
PORT 5.+
2
✓
+
-
6
PORT 5.-
-
PORT 6/
PORT 7
PORT 6.+/
PORT 7.+
3
+
PORT 6.-/
PORT 7.-
-
PORT 7
PORT 7.+
4
+
IO_DA ONLY!
PORT 7.-
-
IO_2M TB6
✓
+
1
+
2
12Vdc
✓
-
3
-
4
+
12V
5V
-
12Vdc
L
~1 kΩ,
N
1/4W
*
+
L
~1 kΩ,
N
1/4W
+
*
L
~1 kΩ,
N
1/4W
+
*
L
~1 kΩ,
N
1/4W
+
*
#1
S
#2
S
#3
S
#4
S