5.2

Topology rules for DRIVE-CLiQ

5.2.1

Topology rules for S120 Combi

Topology rules for DRIVE-CLiQ
There are fixed DRIVE-CLiQ topology rules for the S120 Combi. These rules must be
observed. If these rules are violated, then a corresponding alarm is displayed.
Assigning the DRIVE-CLiQ interfaces
Table 5- 1
Assigning the DRIVE-CLiQ interfaces on the S120 Combi
DRIVE-CLiQ interface
X200
X201
X202
X203
X204
X205
In this case, the TTL encoder interface X220 remains free
1)
Table 5- 2
Assigning the DRIVE-CLiQ interfaces to the SINUMERIK 828D (PPU)
DRIVE-CLiQ interface
X100
X101
X102
When using a TM54F, the DMx20 is connected in series at the TM54F via the DRIVE-CLiQ interface X501
1)
Turning and Milling
Commissioning Manual, 02/2012, 6FC5397-3DP40-3BA0
Connection with
X100 of the PPU
Motor encoder, spindle
Motor encoder, feedrate 1
Motor encoder, feedrate 2
Motor encoder feed 3 → only for 4-axis S120 Combi
Remains empty for 3-axis S120 Combi
Optional: 2. direct sin/cos encoder for spindle (via SMx20)
Remains empty when connecting a direct TTL spindle encoder via X220
Connection with
X200 of the S120 Combi
X200 of a Single Motor Module or Double Motor Module
X500 of the Terminal Module TM54F
X500 of the Hub Modules (DMx20)
Commissioning the drive
5.2 Topology rules for DRIVE-CLiQ
1)
1)