Parameter assignment of a Mobile Client
4.6 General settings
Note
If you change the transfer settings during "Transfer", the new settings only go into effect the
next time the transfer function is started.
This may occur if the Control Panel is opened to change the transfer properties in an active
project.
Procedure
1. In the "Transfer" group, select whether you want to enable or disable transfer.
Select one of the following options:
– Off – Transfer is not possible
– Manual – Manual transfer
– Automatic – Automatic transfer
2. Select the required data channel in the "Transfer channel" group.
– Ethernet
3. Select "Properties" to access HMI device addressing.
You can find the necessary information in "Specifying the IP address and name server
(Page 84)".
4. Confirm your entries.
The dialog closes.
The data channel for transfer is configured.
68
Transfer group
Transfer channel group
Button for the "Network and Dial-Up Connections" dialog; see "Specifying the IP address and
name server (Page 84)"
Press "Transfer" in the Start Center to initiate transfer. The project in progress must be
exited before transfer can be initiated.
The HMI device exits the current project and starts the transferred project.
Note
Automatic transfer is not possible for a fail-safe HMI device.