Mitsubishi Electric MR-J4-*B-RJ010 Series Instruction Manual page 30

General purpose ac servo amplifier cc-link ie field network interface with motion
Hide thumbs Also See for MR-J4-*B-RJ010 Series:
Table of Contents

Advertisement

1. FUNCTIONS AND CONFIGURATION
(e) MR-J4-11KB-RJ010/MR-J4-15KB-RJ010
The broken line area is the same as
MR-J4-200B-RJ010 or less.
(7)
(7)
(6)
(6)
(5)
(Note)
(2)
(2)
(3)
(3)
(4)
(4)
(1)
(1)
Note. Lines for slots around the battery holder are omitted from the illustration.
POINT
The servo amplifier is shown without the front cover. For removal of the front
cover, refer to section 1.7.2 of "MR-J4-_B_(-RJ) Servo Amplifier Instruction
Manual".
No.
(1)
(2)
(3)
(4)
(5)
(6)
(7)
Name/Application
Power factor improving reactor terminal block (TE1-2)
Used to connect a power factor improving DC reactor
and a regenerative option.
Main circuit terminal block (TE1-1)
Used to connect the input power supply and servo
motor.
Control circuit terminal block (TE2)
Used to connect the control circuit power supply.
Protective earth (PE) terminal
Grounding terminal
Battery holder
Install the battery for absolute position data backup.
Rating plate
Charge lamp
When the main circuit is charged, this will light up.
While this lamp is lit, do not reconnect the cables.
1 - 19
Detailed explanation
MR-J4-_B_ section
3.1
MR-J4-_B_ section
3.3
MR-J4-_B_ section
12.2
Section 1.6