6. TROUBLESHOOTING
Display
Description
AC
The synchronous
communications by
specified cycle could not
be made.
b##.
The system has been in
the test operation mode.
C##.
d##.
(Note)
off
Operation mode for
manufacturer setting is
set.
Note. ## indicates axis No.
Cause
MR-J3-T10 is
"AC" is displayed in the
malfunctioning.
corresponding station and
following stations.
The servo amplifier is
"AC" is displayed in the
malfunctioning.
corresponding station and
following stations.
The simple motion
Replace the simple motion
module is malfunctioning.
module and check the
repeatability.
Test operation mode has
Test operation setting switch
been enabled.
(SW2-1) is turned on.
Operation mode for
Check that the test operation
manufacturer setting is
select switch (SW2-1) and
enabled.
manufacturer setting switch
(SW2-2) are not on.
6 - 7
Checkpoint
Replace the MR-J3-T10.
Replace the servo amplifier.
Replace the simple motion
module.
Turn off the test operation setting
switch (SW2-1).
Set the auxiliary station number
setting switches (SW2) correctly.
Action