Ce Compliance - Danfoss VLT AutomationDrive FC 300 Instruction Manual

Hide thumbs Also See for VLT AutomationDrive FC 300:
Table of Contents

Advertisement

Specifications
For further information, please see Application Note Fuses
and Circuit Breakers, MN90TXYY

10.3.3 CE Compliance

Fuses or circuit breakers are mandatory to comply with IEC
60364. Danfoss recommend using a selection of the
following.
Enclosure
FC 300 Power
Size
[kW]
A1
0.25–1.5
A2
0.25–2.2
A3
3.0–3.7
B3
5.5
B4
7.5–15
C3
18.5–22
C4
30–37
A4
0.25–2.2
A5
0.25–3.7
B1
5.5–7.5
B2
11
C1
15–22
C2
30–37
Table 10.10 200–240 V, Frame Sizes A, B, and C
VLT
®
AutomationDrive Instruction
Manual
Recommended
Recommended
fuse size
gG-10
gG-10 (0.25–1.5)
gG-16 (2.2)
gG-16 (3)
gG-20 (3.7)
gG-25
gG-32 (7.5)
gG-50 (11)
gG-63 (15)
gG-80 (18.5)
gG-150 (18.5)
aR-125 (22)
aR-160 (22)
aR-160 (30)
aR-200 (30)
aR-200 (37)
aR-250 (37)
gG-10 (0.25–1.5)
gG-16 (2.2)
gG-10 (0.25–1.5)
gG-16 (2.2–3)
gG-20 (3.7)
gG-25 (5.5)
gG-32 (7.5)
gG-50
gG-63 (15)
gG-160 (15–18.5)
gG-80 (18.5)
aR-160 (22)
gG-100 (22)
aR-160 (30)
aR-200 (30)
aR-200 (37)
aR-250 (37)
®
MG33AL22 - VLT
is a registered Danfoss trademark
The fuses below are suitable for use on a circuit capable of
delivering 100,000 Arms (symmetrical), 240 V, or 480 V, or
500 V, or 600 V depending on the adjustable frequency
drive voltage rating. With the proper fusing the adjustable
frequency drive short circuit current rating (SCCR) is
100,000 Arms.
Recommended circuit
Max. fuse
breaker
Moeller
gG-25
PKZM0-16
gG-25
PKZM0-25
gG-32
PKZM0-25
gG-63
PKZM4-50
gG-125
NZMB1-A100
NZMB2-A200
NZMB2-A250
gG-32
PKZM0-25
gG-32
PKZM0-25
gG-80
PKZM4-63
gG-100
NZMB1-A100
NZMB2-A200
NZMB2-A250
Max. trip level
[A]
16
25
25
50
100
150
250
25
10
10
25
63
100
160
250
10-17

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the VLT AutomationDrive FC 300 and is the answer not in the manual?

Questions and answers

Table of Contents