Specifications
FC 300
Power
[kW]
0.25–0.37
0.55–1.1
1.5
2.2
3.0
3.7
5.5
7.5
11
15–18.5
22
30
37
Table 10.16 200–240 V, Frame Sizes A, B, and C
1) KTS fuses from Bussmann may substitute for KTN for 240 V adjustable frequency drives.
2) FWH fuses from Bussmann may substitute for FWX for 240 V adjustable frequency drives.
3) A6KR fuses from FERRAZ SHAWMUT may substitute for A2KR for 240 V adjustable frequency drives.
4) A50X fuses from FERRAZ SHAWMUT may substitute for A25X for 240 V adjustable frequency drives.
10
10
FC 300
Power
[kW]
0.37–1.1
1.5–2.2
3
4
5.5
7.5
11
15
18
22
30
37
45
55
75
Table 10.17 380–500 V, Frame Sizes A, B, and C
10-22
VLT
Manual
Recommended max. fuse
Bussmann
2)
Type JFHR2
FWX-5
FWX-10
FWX-15
FWX-20
FWX-25
FWX-30
FWX-50
FWX-60
FWX-80
FWX-125
FWX-150
FWX-200
FWX-250
Bussmann
Bussmann
Type RK1
Type J
KTS-R-6
JKS-6
KTS-R-10
JKS-10
KTS-R-15
JKS-15
KTS-R-20
JKS-20
KTS-R-25
JKS-25
KTS-R-30
JKS-30
KTS-R-40
JKS-40
KTS-R-50
JKS-50
KTS-R-60
JKS-60
KTS-R-80
JKS-80
KTS-R-100
JKS-100
KTS-R-125
JKS-125
KTS-R-150
JKS-150
KTS-R-200
JKS-200
KTS-R-250
JKS-250
MG33AL22 - VLT
®
AutomationDrive Instruction
Littel fuse
JFHR2
-
-
-
-
-
-
-
-
-
-
L25S-150
L25S-200
L25S-250
Recommended max. fuse
Bussmann
Bussmann
Type T
Type CC
JJS-6
FNQ-R-6
JJS-10
FNQ-R-10
JJS-15
FNQ-R-15
JJS-20
FNQ-R-20
JJS-25
FNQ-R-25
JJS-30
FNQ-R-30
JJS-40
JJS-50
JJS-60
JJS-80
JJS-100
JJS-125
JJS-150
JJS-200
JJS-250
®
is a registered Danfoss trademark
Ferraz-
Shawmut
4)
JFHR2
-
-
-
-
-
-
-
-
-
-
A25X-150
A25X-200
A25X-250
Bussmann
Type CC
KTK-R-6
KTK-R-10
KTK-R-15
KTK-R-20
KTK-R-25
KTK-R-30
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
Ferraz-
Shawmut
J
HSJ-6
HSJ-10
HSJ-15
HSJ-20
HSJ-25
HSJ-30
HSJ-50
HSJ-60
HSJ-80
HSJ-125
HSJ-150
HSJ-200
HSJ-250
Bussmann
Type CC
LP-CC-6
LP-CC-10
LP-CC-15
LP-CC-20
LP-CC-25
LP-CC-30
-
-
-
-
-
-
-
-
-
Need help?
Do you have a question about the VLT AutomationDrive FC 300 and is the answer not in the manual?
Questions and answers