Wiring To Control Terminals; Using Shielded Control Cables - Danfoss VLT AutomationDrive FC 300 Instruction Manual

Hide thumbs Also See for VLT AutomationDrive FC 300:
Table of Contents

Advertisement

Installation
Terminal description
Default
Terminal Parameter
setting
27
5-12
[2] Coast
inverse
29
5-13
[14] JOG
20
-
37
-
Safe Torque
Off (STO)
Analog inputs/outputs
39
-
42
6-50
[0] No
operation
50
-
+10 V DC
53
6-1*
Reference
54
6-2*
Feedback
55
-
Table 2.4
Terminal description
Default
Terminal Parameter
setting
Serial communication
61
-
68 (+)
8-3*
69 (-)
8-3*
Relays
VLT
®
AutomationDrive Instruction
Manual
Description
Terminal Parameter
Selectable for either
digital input or
01, 02, 03
output. Default setting
04, 05, 06
is input.
Common for digital
Table 2.5 Terminal Description
inputs and 0 V
potential for 24 V

2.4.5.3 Wiring to Control Terminals

supply.
Safe input. Used for
STO.
Control terminal connectors can be unplugged from the
adjustable frequency drive for ease of installation, as
shown in Figure 2.11.
Common for analog
output
Programmable analog
output. The analog
signal is 0–20 mA or
4-20 mA at a
maximum of 500 Ω
10 V DC analog
supply voltage. 15 mA
maximum commonly
used for potenti-
ometer or thermistor.
See 10.1 Power-dependent Specifications for control terminal
Analog input.
wiring sizes.
Selectable for voltage
See 6 Application Examples for typical control wiring
or current. Switches
connections.
A53 and A54 select
mA or V.
Common for analog
input
Description
Integrated RC-Filter for
cable screen. ONLY for
Figure 2.13 Connecting Control Wiring
connecting the shield
when experiencing
EMC problems.

2.4.5.4 Using Shielded Control Cables

RS-485 Interface. A
control card switch is
Correct shielding
provided for
The preferred method in most cases is to secure control
termination resistance.
and serial communication cables with shielding clamps
provided at both ends to ensure best possible high
frequency cable contact.
If the ground potential between the adjustable frequency
drive and the PLC is different, electric noise may occur that
will disturb the entire system. Solve this problem by fitting
®
MG33AL22 - VLT
is a registered Danfoss trademark
Terminal description
Default
setting
[0] No
5-40 [0]
operation
5-40 [1]
[0] No
operation
1.
Open the contact by inserting a small screwdriver
into the slot above or below the contact, as
shown in Figure 2.13.
2.
Insert the bared control wire into the contact.
3.
Remove the screwdriver to fasten the control wire
into the contact.
4.
Ensure the contact is firmly established and not
loose. Loose control wiring can be the source of
equipment faults or less than optimal operation.
1
2
Description
Form C relay output.
2
Usable for AC or DC
voltage and resistive
or inductive loads.
2-9
2

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the VLT AutomationDrive FC 300 and is the answer not in the manual?

Questions and answers

Table of Contents