10.3.2 CE Compliance

Fuses or circuit breakers are mandatory to comply with IEC 60364. Danfoss recommend using a selection of the following.
The fuses below are suitable for use on a circuit capable of delivering 100,000 Arms (symmetrical), 240V, or 480V, or 500V,
or 600V depending on the Adjustable frequency drive voltage rating. With the proper fusing, the Adjustable frequency drive
short circuit current rating (SCCR) is 100,000 Arms.
Enclosure
FC 300 Power
Size
[kW]
A1
0.25–1.5
A2
0.25–2.2
A3
3.0–3.7
B3
5.5
B4
7.5–1.5
C3
18.5–22
C4
30–37
A4
0.25–2.2
A5
0.25–3.7
B1
5.5–7.5
B2
11
C1
15–22
C2
30–37
Table 10.1 200–240V, Frame Sizes A, B, and C
VLT
®
AutomationDrive Instruction
Manual
Recommended
Recommended
fuse size
gG-10
gG-10 (0.25–1.5)
gG-16 (2.2)
gG-16 (3)
gG-20 (3.7)
gG-25
gG-32 (7.5)
gG-50 (11)
gG-63 (15)
gG-80 (18.5)
gG-150 (18.5)
aR-125 (22)
aR-160 (22)
aR-160 (30)
aR-200 (30)
aR-200 (37)
aR-250 (37)
gG-10 (0.25–1.5)
gG-16 (2.2)
gG-10 (0.25–1.5)
gG-16 (2.2–3)
gG-20 (3.7)
gG-25 (5.5)
gG-32 (7.5)
gG-50
gG-63 (15)
gG-160 (15–18.5)
gG-80 (18.5)
aR-160 (22)
gG-100 (22)
aR-160 (30)
aR-200 (30)
aR-200 (37)
aR-250 (37)
®
MG.33.AI.22 - VLT
is a registered Danfoss trademark
Recommended circuit
Max. fuse
breaker
Moeller
gG-25
PKZM0-16
gG-25
PKZM0-25
gG-32
PKZM0-25
gG-63
PKZM4-50
gG-125
NZMB1-A100
NZMB2-A200
NZMB2-A250
gG-32
PKZM0-25
gG-32
PKZM0-25
gG-80
PKZM4-63
gG-100
NZMB1-A100
NZMB2-A200
NZMB2-A250
Max. trip level
[A]
16
25
25
50
100
150
250
25
25
10
10
63
100
160
250
10-17