Digital Outputs (X3) - Beckhoff AX2040 Assembly, Installation, Setup

Digital servo amplifier
Hide thumbs Also See for AX2040:
Table of Contents

Advertisement

Beckhoff
4.7.4

Digital outputs (X3)

Technical characteristics
Ready-to-operate contact BTB/RTO
Operational readiness (terminals X3/2 and X3/3 ) is signalled by a floating relay contact.
The contact is closed when the servo amplifier is ready for operation, the signal is not influenced
by the enable signal, the I²t- limit, or the regen threshold.
All faults cause the BTB/RTO contact to open and the switch-off of the output
stage (if the BTB contact is open, the output stage is disabled -> no power). A list
of the error messages can be found on page 70.
Programmable digital outputs DIGITAL-OUT 1 / 2:
You can use the digital outputs DIGITAL-OUT1 (terminal X3/16) and DIGITAL-OUT2 (terminal
X3/17) to outputs messages from pre-programmed functions that are stored in the servo amplifier.
You can find a list of pre-programmed functions on the "digital I/O" screen of our setup software.
If an input is freshly assigned to a pre-programmed function, then the data set must be stored in the
EEPROM of the servo amplifier, and the 24V auxiliary supply of the servo amplifier must be swit-
ched off and on again (to reset the amplifier software).
Evaluate the outputs via inverting interface relays (see connection diagram), for example
Phönix DEK-REL-24/I/1 (turn-on delay 6 ms, turn-off delay 16ms).
The described logic in the SETUP SOFTWARE manual refers to the output of the
inverting interface relays. Consider the delay of the applied relay !
AX2040/2070 Installation Manual
Reference ground is digital-GND (DGND, terminal X3/18)
All digital outputs are floating
DIGITAL-OUT1 and 2
BTB/RTO
Update rate 250 µs
AX2040/2070
02/06
: Open-collector, max. 30VDC, 10 mA
: Relay output, max. 30VDC or 42VAC, 0.5A
Interfaces
- A.4.031.1/20
55