Transport, storage, maintenance, disposal
Transport :
Packaging:
Storage :
Maintenance :
Cleaning :
Disposal :
AX2040/2070 Installation Manual
02/06
— only by qualified personnel
— only in the manufacturer's original recyclable packaging
— avoid shocks
— temperature
–25 to +70°C (-13...158°F), max. 20k/hr rate of change
— humidity
max. 95% relative humidity, no condensation
— the servo amplifiers contain electrostatically sensitive components which can
—
be damaged by incorrect handling
—
Discharge yourself before touching the servo amplifier. Avoid contact with
—
highly insulating materials (artificial fabrics, plastic films etc.).
—
Place the servo amplifier on a conductive surface.
— if the packaging is damaged, check the unit for visible damage.
—
In this case, inform the shipper and the manufacturer.
— Cardboard box with foam padding, can be recycled
— Dimensions: (HxWxD) 410x470x490 mm
— Gross weight, accessories included, approx. 25 Kg
— only in the manufacturer's original recyclable packaging
— the servo amplifiers contain electrostatically sensitive components which can
—
be damaged by incorrect handling
—
Discharge yourself before touching the servo amplifier. Avoid contact with
—
highly insulating materials (artificial fabrics, plastic films etc.),
—
Place the servo amplifier on a conductive surface.
— max. stacking height:
— storage temperature–
— humidity
— storage duration
— the instruments do not require any maintenance
— opening the instruments invalidates the warranty
— if the casing is dirty : cleaning with Isopropanol or similar
do not immerse or spray
— if there is dirt inside the unit:
— dirty protective grill (fan):
— the servo amplifier can be reduced to its principal components by unscrewing
—
it (aluminium heat sink and front panel steel housing sections, electronics
—
boards)
— disposal should be carried out by a certified disposal company.
—
We can give you suitable addresses.
3 cartons
25 to +55°C(-13...131°F),
max. 20K/hr. rate of change
relative humidity 5...95%, no condensation
< 1 year without restriction
> 1 year : capacitors must be re-formed before
setting up the servo amplifier.
To do this, remove all electrical connections and
supply the servo amplifier for about 30 min from
230VAC, single-phase, on terminals L1 / L2.
to be cleaned by the manufacturer
clean with a dry brush
Appendix