Installation / Setup

2.15.5.1

Safety instructions

l
l
l
l
2.15.5.2

Functional test

The functioning of the restart lock must be tested during setup, after every alteration in the wiring of
the system, or after exchanging one or more components of the system.
1.
2.
3.
4.
5.
6.
2.15.5.3

Connection diagram

AX2040/2070 Installation Manual
Observe the prescribed use of the restart lock -AS- (ð p. 10)
The monitoring contacts (KSO1/2) for each amplifier must be looped into the control
circuit. This is vital, so that a malfunction of the internal safety relay or a cable break
can be recognized.
If the restart lock -AS- is automatically activated by a control system (KSI1/2), then
make sure that the output of the control is monitored for possible malfunction. This
can be used to prevent a faulty output from activating the restart lock -AS- while the
motor is running.
Keep to the following functional sequence when the restart lock -AS- is used :
1.
Brake the drive in a controlled manner (speed setpoint = 0V)
2.
When speed = 0 rpm, disable the servo amplifier (enable = 0V)
3.
If there is a suspended load, block the drive mechanically
4.
Activate the restart lock -AS-
Stop all drives, with setpoint 0V, disable drives,
mechanically block any suspended loads
Activate the restart lock -AS-.
Open protective screens (but do not enter hazardous area)
Pull off the X10 connector from an amplifier: the mains contactor must drop out
Reconnect X10. Switch on mains contactor again.
Repeat steps 4 and 5 for each individual servo amplifier.