Change Hardware Configuration Offline - Siemens SIMATIC CPU 410 System Manual

Process control system, process automation/cpu
Table of Contents

Advertisement

Plant changes during redundant operation - H-CiR
12.9 Removal of components
The modules to be removed and their connected sensors and actuators are no longer of any
significance to the process being controlled. The fault-tolerant system is operating in the
redundant system state.
Procedure
Follow the steps below to remove hardware components from a fault-tolerant system in
SIMATIC PCS 7. Details of each step are described in a subsection.
Step
What to do?
1

Change hardware configuration offline

2
Editing and downloading the user program
3
Access H-CiR wizard
4
Modification of hardware
Exceptions
This procedure for plant changes does not apply for removing interface modules
(see Removal of interface modules (Page 216)).
12.9.1
Change hardware configuration offline
Starting situation
The fault-tolerant system is operating in the redundant system state.
Procedure
1. Perform offline only the configuration modifications relating to the hardware being
removed. As you do, delete the icons to the channels that are no longer used.
2. Compile the new hardware configuration but do not yet download it to the PLC.
Result
The modified hardware configuration is available in the PG/ES. The target system continues
operation with the old configuration in redundant system mode.
212
See section
Change hardware configuration offline
(Page 212)
Modify and download the user program
(Page 213)
The H-CiR wizard (Page 197)
Modify hardware (Page 215)
CPU 410 Process Automation/CPU 410 SMART
System Manual, 05/2017, A5E31622160-AC

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Simatic 410 smartSimatic pcs 7

Table of Contents