Replacement of failed components during redundant operation
13.3 Replacement of components of the distributed I/O on PROFIBUS DP
Replacement of signal and function modules
Note the different procedures.
Minor injury or damage to equipment is possible.
The procedure for replacing and input/output or function module differs for modules of the
S7-300 and S7-400.
Use the correct procedure when replacing a module. The correct procedure is described
below for the S7-400 in Chapter Replacement of an input/output module or function module
(Page 226).
To replace signal and function modules of an S7-300, perform the following steps:
Step
What to do?
1
Disconnect the module from its load current supply.
2
Remove the failed module (in RUN mode).
3
Disconnect the front connector and wiring.
4
Plug the front connector into the new module.
5
Insert the new module.
13.3.1

Replacement of a PROFIBUS DP master

Starting situation
Failure
The S7-400H is in the redundant system state
and a DP master module fails.
234
CAUTION
How does the system react?
Both CPUs generate a remove/insert
interrupt and enter the event in the diagnostic
buffer and the system status list.
-
-
Both CPUs generate a remove/insert
interrupt and enter the event in the diagnostic
buffer and the system status list.
Parameters are assigned automatically to the
module by the CPU concerned and the module is
addressed again.
How does the system react?
With single-channel one-sided I/O:
The DP master can no longer process con-
nected DP slaves.
With switched I/O:
DP slaves are addressed over the DP master
of the partner.
CPU 410 Process Automation/CPU 410 SMART
System Manual, 05/2017, A5E31622160-AC