Delete all CiR elements of an existing DP master system as follows:
1. Highlight the icon of the corresponding DP master system in the upper part of the station
window.
2. Select the command "Master system > Disable CiR compatibility" in the Edit menu.
STEP 7 will then delete
● all CiR objects in sublevel PA master systems
● all CiR modules in modular slaves
● the CiR object at the selected DP master system.
Deleting a Single CiR Element
You can delete the CiR object from a PA master system or ET200M /ET200iSP modular DP
slave as follows:
1. Highlight the CiR element you want to delete.
2. Select "Edit > Delete" or the context-sensitive menu command Delete.
If no more CiR elements exist at the DP master system, save for the CiR object, you can use
the same procedure to delete this CiR object.
11.8.2

Basic Procedure in RUN Mode

11.8.2.1

Overview

Overview
The following basic operating steps are available in RUN:
● Add slaves or modules
● Rebuild hardware when adding a slave
● Change process image partition assignment
● Re-configure existing modules in ET 200M/ET 200iSP stations
● Undo previously made changes (Undo functionality)
● Replace slaves or modules
CPU 410 Process Automation/CPU 410 SMART
System Manual, 05/2017, A5E31622160-AC
Plant changes in RUN - CiR
11.8 Procedure for PROFIBUS DP