Configuration of the CPU 410
3.2 CPU 410 monitoring functions
Type of error
Failure of a rack/station
Communication error
Execution canceled
Missing license for Runtime
software
Programming error
MC7 code error
40
Cause of error
Power failure in an S7-400 expansion unit
Failure of a DP/PN segment
Failure of a coupling segment: Missing or defective IM, inter-
rupted cable
Communication error:
Time synchronization
Access to DB when exchanging data via communications func-
tion blocks
The execution of a program block was canceled. Possible reasons
for the cancellation are:
Nesting depth of nesting levels too great
Nesting depth of master control relay too great
Nesting depth of synchronization errors too great
Nesting depth of block call commands (U stack) too great
Nesting depth of block call commands (B stack) too great
Error during allocation of local data
Such errors cannot occur with blocks from a SIMATIC PCS 7 li-
brary.
The Runtime software could not be completely licensed (internal
error).
User program error:
BCD conversion error
Range length error
Range error
Alignment error
Write error
Timer number error
Counter number error
Block number error
Block not loaded
Such errors cannot occur with blocks from a SIMATIC PCS 7 li-
brary.
Error in the compiled user program, for example, illegal OP code or
a jump beyond the block end
Such errors cannot occur with blocks from a SIMATIC PCS 7 li-
brary.
Error LED
EXTF
BUSF for PN and DP
REDF for redundant
segments
INTF
INTF
INTF
INTF
INTF
CPU 410 Process Automation/CPU 410 SMART