Technical data
16.2 Technical specifications of CPU 410E (6ES7410-5HM08-0AB0)
Article number
expandable
Load memory
integrated RAM, max.
expandable RAM
Backup
present
with battery
without battery
Battery
Backup battery
Backup current, typ.
Backup current, max.
Backup time, max.
Feeding of external backup voltage to CPU No
CPU processing times
CPU speed
average processing time of PCS 7 typicals
Process tasks, max.
CPU-blocks
DB
Number, max.
FB
Number, max.
FC
Number, max.
OB
Number of free cycle OBs
Number of time alarm OBs
Number of delay alarm OBs
Number of cyclic interrupt OBs
Number of process alarm OBs
Number of DPV1 alarm OBs
Number of startup OBs
Number of asynchronous error OBs
Number of synchronous error OBs
264
6ES7410-5HM08-0AB0
Dependent on the System Expansion Card used
48 Mbyte
No
Yes
Yes; all data
Yes; Program and data of the load memory
370 µA; Valid up to 40°C
2.1 mA
Dealt with in the module data manual with the
secondary conditions and the factors of influence
450 MHz; Multi-processor system
110 µs; with APL Typicals
9; Individually adjustable from 10 ms to 5 s
16 000; Number range: 1 to 16 000 (= Instances)
8 000; Number range: 0 to 7999
8 000; Number range: 0 to 7999
1; OB 1
8; OB 10-17
4; OB 20-23
9; OB 30-38 (= Process Tasks)
8; OB 40-47
3; OB 55-57
2; OB 100, 102
9; OB 80-88
2; OB 121, 122