Plant changes in RUN - CiR

11.3 Procedure for PROFINET IO

Restriction
All changes that are not explicitly permitted above as part of plant changes in RUN, are not
permitted during operation and are not explained in more detail here.
Recommendations plant changes during operation using CiR
● Create a backup copy of your current plant configuration after every modification of the
configuration. Further processing of the project without loss of CiR capability is only
possible with this backup version.
● If possible, change the configuration in multiple steps and make only a few changes in
each step. In this way, you can keep track of the changes.
11.3
Procedure for PROFINET IO
11.3.1

Overview

Requirement
You need to load the hardware configuration from HW Config to the module in STOP
Note
You do not have to define CiR elements in PROFINET IO subsystems.
Procedure
The following basic operating steps are available in RUN mode:
● Add or remove IO devices or I/O modules
IO devices and I/O modules can be added and removed in the same step.
● Rebuild hardware when adding an IO device
● Change process image partition assignment
● Re-configure existing modules or I/O modules
● Undo previously made changes (Undo functionality)
158
CPU 410 Process Automation/CPU 410 SMART
System Manual, 05/2017, A5E31622160-AC