Properties and technical specifications of CPU 410 SMART
17.2 Technical specifications of the CPU 410 SMART; (6ES7 410-5HN08-0AB0)
Article number
Number of stations in the ring, max.
Functionality
PROFINET IO Controller
PROFINET IO Device
PROFINET CBA
Open IE communication
Web server
PROFINET IO Controller
Transmission rate, max.
Services
PG/OP communication
S7 routing
S7 communication
Open IE communication
Shared device
Prioritized startup
Number of connectable IO Devices,
max.
Number of connectable IO Devices for
RT, max.
of which in line, max.
Activation/deactivation of IO Devices
IO Devices changing during operation
(partner ports), supported
Device replacement without swap me-
dium
Send cycles
Updating time
Address area
Inputs, max.
Outputs, max.
User data consistency, max.
Open IE communication
Number of connections, max.
Local port numbers used at the system end 0, 20, 21, 25, 102, 135, 161, 34962, 34963,
Keep-alive function, supported
290
6ES7410-5HN08-0AB0
50
Yes
No
No
Yes
No
100 Mbit/s
Yes
Yes
Yes
Yes
No; however, usable as part of S7
No
48
48
48
Yes; Single mode only
No
Yes
250 µs, 500 µs, 1 ms, 2 ms, 4 ms
250 µs to 512 ms, minimum value depends on
the number of configured user data and the con-
figured single or redundant mode
1 536 byte; Up to 1 500 IOs (channels)
1 536 byte; Up to 1 500 IOs (channels)
1 024 byte
118
34964, 65532, 65533, 65534, 65535
Yes
CPU 410 Process Automation/CPU 410 SMART
System Manual, 05/2017, A5E31622160-AC