Table 6- 2 Measures In Profisafe For Error Avoidance - Siemens SIMATIC CPU 410 System Manual

Process control system, process automation/cpu
Table of Contents

Advertisement

I/O configuration variants
6.2 Fail-safe operation
PROFINET IO is the innovative and open Industrial Ethernet standard for automation. It
enables fast reaction times and transmission of large data quantities.
PROFIsafe uses the PROFIBUS or PROFINET IO services for safe communication. A fail-
safe CPU 410 and the fail-safe I/O exchange both user data as well as status and control
information; no additional hardware is required for this.
PROFIsafe takes the following measures to counteract the various possible errors when
transferring messages.
Table 6- 2
Measures in PROFIsafe for error avoidance
Measure/
Error
Repetition
Loss
Insertion
Incorrect sequence
Data falsification
Delay
Coupling of safety-
related messages and
standard messages
(masquerade)
FIFO errors (first-in-
first-out data register
for maintaining the
sequence)
See also
S7 F Systems optional package
(http://support.automation.siemens.com/WW/view/en/35130252)
60
Consecutive number
Time expectation with
acknowledgment
Identifier for sender
Data backup CRC
and receiver
CPU 410 Process Automation/CPU 410 SMART
System Manual, 05/2017, A5E31622160-AC

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Simatic 410 smartSimatic pcs 7