Article number
–
Updating time
Address area
–
Inputs, max.
–
Outputs, max.
–
User data consistency, max.
Open IE communication
Number of connections, max.
•
Local port numbers used at the system end 0, 20, 21, 25, 102, 135, 161, 34962, 34963,
•
Keep-alive function, supported
•
3. Interface
Interface type
Physics
Isolated
automatic detection of transmission rate
Autonegotiation
Autocrossing
System redundancy
Redundant subnetworks
Number of connection resources
Interface types
Number of ports
•
integrated switch
•
Media redundancy
supported
•
Switchover time on line break, typ.
•
Number of stations in the ring, max.
•
Functionality
PROFINET IO Controller
•
PROFINET IO Device
•
PROFINET CBA
•
Open IE communication
•
Web server
•
PROFINET IO Controller
Transmission rate, max.
•
Services
–
PG/OP communication
CPU 410 Process Automation/CPU 410 SMART
System Manual, 05/2017, A5E31622160-AC
16.1 Technical specifications of CPU 410-5H; (6ES7410-5HX08-0AB0)
6ES7410-5HX08-0AB0
250 µs to 512 ms, minimum value depends on
the number of configured user data and the con-
figured single or redundant mode
8 kbyte; up to 3 800 IOs (channels)
8 kbyte; up to 3 800 IOs (channels)
1 024 byte
118
34964, 65532, 65533, 65534, 65535
Yes
PROFINET
Ethernet RJ45
Yes
Yes; Autosensing
Yes
Yes
Yes
Yes
120
2
Yes
Yes
< 200 ms
50
Yes
No
No
Yes
No
100 Mbit/s
Yes
Technical data
259