Redundant DO dual-channel
DO8xDC 24 V/0.5 A
Definite evaluation of the diagnostics information "P short-circuit" and "wire break" is not possible. Deselect these individu-
ally in your configuration.
DO8xDC 24 V/2 A
DO32xDC 24 V/0.5 A
DO8xAC 120/230 V/2 A
DO 4x24 V/10 mA [EEx ib]
You cannot use the module in redundant operation for applications in hazardous areas.
DO 4x15 V/20 mA [EEx ib]
You cannot use the module in redundant operation for applications in hazardous areas.
DO 16xDC 24 V/0.5 A
The equipotential bonding of the load circuit should always be at one point only (preferably load minus).
Diagnostics of the channels is not possible.
DO 16xDC 24 V/0.5 A
The equipotential bonding of the load circuit should always be at one point only (preferably load minus).
DO 10xDC 24 V/2 A
F module in standard mode
Redundant AI dual-channel
AI8x12Bit
Use in voltage measurement
The "wire break" diagnostics function in HW Config must not be enabled either the modules are operated with transmit-
ters or when thermocouples are connected.
Use for indirect current measurement
When determining the measuring error, observe the following: The total input resistance in measuring ranges > 2.5 V is
reduced from a nominal 100 kilohms to 50 kilohms when you operate two inputs connected in parallel.
The "wire break" diagnostics function in HW Config must not be enabled either the modules are operated with transmit-
ters or when thermocouples are connected.
Use a 50 ohm resistor (measuring range +/- 1 V) or 250 ohm resistor (measuring range 1 to 5 V) to map the current on
a voltage. The tolerance of the resistor must be added on to the module error.
This module is not suitable for direct current measurement.
Use of redundant encoders:
You can use a redundant encoder with the following voltage settings:
+/- 80 mV (only without wire break monitoring)
+/- 250 mV (only without wire break monitoring)
+/- 500 mV (wire break monitoring not configurable)
+/- 1 V (wire break monitoring not configurable)
+/- 2.5 V (wire break monitoring not configurable)
+/- 5 V (wire break monitoring not configurable)
+/- 10 V (wire break monitoring not configurable)
1...5 V (wire break monitoring not configurable)
CPU 410 Process Automation/CPU 410 SMART
System Manual, 05/2017, A5E31622160-AC
6.7 Connection of two-channel I/O to the PROFIBUS DP interface
I/O configuration variants
Article No.
6ES7322-8BF00-0AB0
6ES7322-1BF01-0AA0
6ES7322-1BL00-0AA0
6ES7322-1FF01-0AA0
6ES7322-5SD00-0AB0
6ES7322-5RD00-0AB0
6ES7322-8BH01-0AB0
6ES7322-8BH10-0AB0
6ES7326-2BF00-0AB0
6ES7326-2BF01-0AB0
6ES7331-7KF02-0AB0
85