Longest response time
The figure below shows the conditions under which the longest response time is achieved.
Figure 18-33 Longest response time
Calculation
The (longest) response time is calculated as follows:
● 2 x process image transfer time of the inputs +
● 2 x process image transfer time of the outputs +
● 2 x operating system processing time +
● 2 x program processing time +
● 2 x delay of the DP slave frame (including processing in the DP master) +
● Delay of the inputs and outputs
This is equivalent to the sum of twice the cycle time and the delay in the inputs and outputs
plus twice the DP cycle time.
CPU 410 Process Automation/CPU 410 SMART
System Manual, 05/2017, A5E31622160-AC
Supplementary information
18.16 CPU 410 cycle and reaction times
367